Cables And Connectors; Power Supply Connections; Figure 103: Mounting Panel To Install Two Remote Acquisition Modules (Ra331/332) In A - GE RPV311 Technical Manual

Distributed multifunction fault recorder
Table of Contents

Advertisement

Chapter 15 – Installation
Figure 103: Mounting panel to install two remote acquisition modules (RA331/332) in a 19-inch rack
4

Cables and Connectors

5

Power Supply Connections

RPV311-TM-EN-7
This section describes the type of wiring and connections that should be used when
installing the device. For pin-out details please refer to the Hardware Design chapter
or the wiring diagrams.
Before carrying out any work on the equipment you should be
familiar with the Safety Section and the ratings on the
equipment's rating label.
The connections: Console1, Console2, MODEM and Process bus
are non-isolated and for local connection only.
The RPV311, RA331, RA332 and RA333 can be powered-up by DC or AC power source
within the limits specified in Chapter 17: Technical Specifications.
The power connections shall use insulated flexible conductors anti-flame (BWF type)
with 1.5 mm² section, thermal class 70 °C and isolation voltage of 750 V.
To reduce risk of electrical shock, pre-insulated pin terminals, as shown in Figure 104,
should be used on the ends of the power connections.
RPV311
217