In order to configure the analog input to measure current signals, remove all
connectors and cables which are connected to the module and remove the back
panel of the RA331, RA332 or RA333, removing the 12 screws of the panel and the
screw of the protective grounding, as shown in
Figure 119: Screws of the Back Panel
Remove the board corresponding to the channel to be configured. For each channel
to be configured for current, connect the jumper between positions 2 and 3 as shown
in
Figure 120.
Figure 120: Internal Jumper
Chapter 15 – Installation
Figure 119