Ra331, Ra332 And Ra333 Mechanical Installation; Figure 102: Minimum Distances For The Equipment Mounting - GE RPV311 Technical Manual

Distributed multifunction fault recorder
Table of Contents

Advertisement

RPV311
3.2

RA331, RA332 and RA333 Mechanical Installation

3.2.1
Panel for Installation of Two Remote Acquisition Modules
(Q61)
RPV311-TM-EN-7

Figure 102: Minimum distances for the equipment mounting

The screws for fixing the equipment are of the M6 type.
The curvature of fiber-optic connected to the back of the equipment must have a
minimum radius of 30 mm.
The fixing screws are not included in the product order.
To install the module in the panel, make a cut with the drilling and dimensions
described in Section 23.1.1. The screws used for fixation are of the M6 type.
It is possible to order an optional panel for installation of one or two modules
adapted to a 19-inch rack.
To install either a single or two modules of RA331, RA332 or RA333 it is available for
ordering the optional panels presented below. The screws used for fixing are of the
M6 type.
The Mounting panel to install two remote acquisition modules (RA331/332) in a 19-
inch rack is shown in
Figure
103.