Chapter 15 – Installation
RPV311-TM-EN-7

Figure 115: Screws of the Back Panel

Remove the board corresponding to the channel to be configured. In order to
configure a channel for voltage, connect the jumper between positions 1 and 2 as
shown in
Figure 116.

Figure 116: Internal Jumper

Place the board back in the case.
Secure the case by screwing the back panel and connecting the terminal cables.
Connections shall use insulated flexible wires of 1.5 mm² cross section, 8 mm ring
terminals, and M3 holes.
RPV311
225