GE RPV311 Technical Manual page 260

Distributed multifunction fault recorder
Table of Contents

Advertisement

RPV311
RPV311-TM-EN-7
IEC 61000-4-
11:2004
IEC 61000-4-
29:2000
IEC 61000-4-
16:1998+A2:2009
Chapter 17 – Technical Specifications
A.C. and d.c. voltage dips
Test level: 0% residual voltage
Duration time
a.c.: 1 cycle
d.c.: 16,6ms
Test level: 40% residual voltage
Duration time
a.c.: 12 cycles
d.c.: 200ms
Test level: 70% residual voltage
Duration time
a.c.: 30 cycles
d.c.:500ms
A.C. and d.c. voltage interruptions
Test level: 0% residual voltage
Duration time
a.c.: 300 cycles
d.c.: 5s
Test frequency: Test frequency: 16,7 Hz, 50 Hz
and 60 Hz
Test Voltage: 100V (differential mode) with 1 sec
dwell time
-Coupling resistor 100 Ω
-Coupling capacitor 0,047µF
300V (common mode) with 1 sec dwell time
-Coupling resistor 200 Ω
-Coupling capacitor 0,47µF
260