DETAILS OF THE MODULATION CONTROL MOTOR SQM 10 AND SQM 20 FOR REGULATION OF CAMS

To modify the regulation of the 3 cams utilized, operate the respective red rings ( A - Z - M ).
By pushing with enough force, in the direction desired, each red ring will rotate with respect to the reference scale.
The index of the red ring indicates on the respective reference scale the rotation angle taken up for each cam.
Adjustable Cams
Maximum air opening
end of the run
Maximum air opening
end of the run
B = Insertion and disinsertion lever
17 / 26
0006080767_201002
Reference Index
Camsshaft
Air ignition opening
motor connection Camshaft
Position 1 = Disinsertion
Position 2 = Insertion