Daikin DCM601A51 Commissioning Manual page 83

Hide thumbs Also See for DCM601A51:
Table of Contents

Advertisement

Scene
Failure mode
Impact to users
Leakage
Manual
Leakage Check
Check
Check Start
cannot be run
instruction
failure
S c h e d u l e d
Leakage Check
Check Start
cannot be run
failure
iTM judged that
• Output of incorrect
it successfully
check results
started
• Inability to cancel
Leakage
"Under Maintenance"
Check, but
status until 180
outdoor unit has
minutes have
not started
elapsed
Leakage Check
iTM judged that
• Outdoor unit
it failed to start
remains in a
Leakage
Leakage Check run,
Check, but
cooling indoor air
outdoor unit has
unintendedly
started
• Ability to re-send
Leakage Check
Leakage Check
instruction to
outdoor units under
maintenance
iTM judged that
• Outdoor unit
it completed
remains in a
Leakage
Leakage Check run,
Check, but
cooling indoor air
outdoor unit has
unintendedly
not stopped
• Ability to re-send
Leakage Check
Leakage Check
instruction to
outdoor units under
maintenance
Cause
• Outdoor units are
under maintenance
• Outdoor units are
communication error
• Outdoor units are
auto charge not
completed
• Indoor units are
equipment error
• Indoor units are
under maintenance
• Indoor units are in
emergency stop
The Check Start
instruction was sent
to an outdoor unit,
but the sending
attempt failed due to
a communication
error and then iTM
was turned OFF
before it judges that
the sending attempt
was failed
The Check Start
instruction was sent
to an outdoor unit to
start a Leakage
Check run, but
communication with
the outdoor unit was
disconnected before
iTM receives a
response
Communication was
disconnected when
Leakage Check was
stopped, but iTM has
not yet judged that it
is a communication
error
Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
Handling
Notification method
When
How
When the
• Cause of failure is
[Check Start]
displayed as an
button is
error message
touched
• Cause of failure is
recorded in the
history
At schedule
• Cause of failure is
trigger
recorded in the
history
When an iTM
• Maintenance status
start time of
is canceled and
180 minutes
Leakage Check
has elapsed
results are made
since the
viewable
start of
Leakage
Check
• When the
• Leakage Check
Check Start
Start failure is
instruction was
recorded in the
sent
history
• When a
• Communication
communication
failure is recorded
error occurred
into the history
• When the
• Leakage Check
Check Stop
Stop failure is
instruction was
recorded in the
sent
history
• When a
• Communication
communication
failure is recorded
error occurred
into the history
Recovery method
Touch the [Check
Start] button again
after recovering the
cause of failure
Set up the schedule
again after
recovering the cause
of failure
Touch the Check
Start button or set up
the schedule again
after recovery from
the cause of failure
Solve the
communication error
and start a Leakage
Check run again
when an iTM start
time of 180 minutes
has elapsed
Solve the
communication error
and start a Leakage
Check run again
when an iTM start
time of 180 minutes
has elapsed
82