Daikin DCM601A51 Commissioning Manual page 31

Hide thumbs Also See for DCM601A51:
Table of Contents

Advertisement

(44)
Upper Limit field
Sets up the upper limit and monitoring status for upper limit error monitoring.
For the upper limit, touch the Modify button and enter it in the Numerical Input dialog that
appears.
For the monitoring status, select from Disable, Monitoring, and Monitor + History from the combo
box.
(45)
Analog Type radio button
Select the analog value type from Temperature and Other.
(46)
Unit Type radio button
Select the unit type of External Ai either "Thermistor" or "Other". The unit type cannot be
configured when Other is selected in Analog Type (45).
Selecting Thermistor sets the Minimum value and Maximum value text fields
512.0 (or –890 and 954 in Fahrenheit), respectively, which cannot be changed.
(47)
Minimum Value / Maximum Value text field
Sets up the physical quantities corresponding to the minimum and maximum analog value input
signals.
Touch the Modify button and enter the value in the Numerical Input dialog that appears.
(48)
Reference settings field
Sets up the Target Point and Target analog value for the Internal Ai.
Touch the Ref.. button and select the Target Point and Target analog value to set from the Analog
Point Selection screen that appears (see page 32).
Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
(47)
to –512.0 and
30