Daikin DCM601A51 Commissioning Manual page 24

Hide thumbs Also See for DCM601A51:
Table of Contents

Advertisement

The range of values you can enter/set is as indicated in the table below.
Detailed
Type
View
Di/Pi
D3Di
D3Dio
Indoor unit
Ventilator
D3Chiller
Outdoor unit
Internal Ai
×
Internal Pi
(16)
Detailed Type field
Displays the detailed management point type. However, you cannot modify it here.
(17)
Mgmt. Pt. ID field
Displays the management point ID automatically allocated by the system. However, you cannot
modify it here.
(18)
Name text field
Sets up the management point name.
Touch the Modify button and enter the name in the Name Input dialog that appears.
Specify a name for the management point using 1 to 12 characters, irrespective of single or
double byte.
(19)
Detailed Info. text field
Set up information about the management point as necessary.
Touch the Modify button and enter the value in the Text Input dialog that appears.
The number of characters you can enter is 0 to 50, irrespective of single or double byte.
(20)
Icon field
Sets up the icon for the management point.
Touch the Modify button and set the icon in the Icon Setup screen that appears.
23
Port number
Minimum/Maximum value
(Default value)
1 to 8 (1)*
1 to 8 (1)
1 to 8 (1)
1 to 8 (1)
1 to 8 (1)
1 to 8 (1)
1 to 8 (1)
-
1 to 8 (1)
* The combination: Port number 1 and Address 1 is assigned exclusively
for the input of the iTM unit emergency stop signal and cannot be used.
Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
Address
View
Minimum/Maximum value
(Default value)
Non-differentiated
1 to 4 (2)*
1-00 to 4-15 (1-00)
1-00 to 4-15 (1-00)
1-00 to 4-15 (1-00)
1-00 to 4-15 (1-00)
1-00 to 4-15 (1-00)
×
×
×
-
-
-