NOTE
• The calculated leakage amount is only a guide.
• The check result may not be correct if the power is lost during leakage check.
CAUTION
• Leakage check may fail depending on the room temperature.
Moderate the room temperature by conducting the cooling or heating operation before
starting leakage check.
* Recommended temperature
Room temperature: 22°C – 30°C
Outdoor temperature: 5°C – 35°C
• The indoor unit stops after a leakage check.
However, indoor units not connected to the remote control continue operating.
Furthermore, these indoor units may operate in a different mode from that before the leakage
check.
For this reason, set up a schedule to stop or start the indoor units in a specific operation
mode as required.
(Set up the schedule to stop/start the indoor units after 180 minutes from the start of the
leakage check since iTM leakage check ends after 180 minutes.)
Check with the building janitor for any inconvenience if indoor units are stopped after the
leakage check.
• Always check the following in the history before checking the leakage check results.
Leakage check fails if an equipment error occurs during leakage check. Run leakage check
again after clearing the cause of the error.
Commissioning Manual EM11A021