NOTICE
7.4.2

Input conductors

Customer supplied
S
May consist either of heavy rubber covered copper conductors (three power and
S
one ground) or run in solid or flexible conduit.
Sized according to the chart.
S
7.4.3

Input connection procedure

Power input cable access
1
opening (rear panel)
1. Remove small rear panel of the EPP-360.
2. Thread cables through the access opening in the rear panel.
3. Secure cables with strain relief at the access opening.
4. Connect the ground lead to the stud on the chassis.
5. Connect the power leads to the primary terminals.
6. Connect the input conductors to the line (wall) disconnect.
7. Before applying power, replace the rear cover panel.
bp12a1
Dedicated power line may be necessary.
EPP-360 is equipped with line voltage compensation but to
avoid impaired performance due to an overloaded circuit, a
dedicated power line may be required.
I
MPROPER GROUNDING CAN RESULT IN DEATH OR INJURY.
CHASSIS MUST BE CONNECTED TO AN APPROVED
ELECTRICAL GROUND. BE SURE GROUND LEAD IS NOT
CONNECTED TO ANY PRIMARY TERMINAL.
Chassis ground
2
- 19 -
Primary terminals
3