Conformity to the Low Voltage Directive in the EU (Continued)
9. Use wires listed in EN60204 Appendix C.
Inverter type
̈
FRN0.75AR1
-4¸
0.75
̈
1.5
FRN1.5AR1
-4¸
̈
2.2
FRN2.2AR1
-4¸
̈
̈
3.7
FRN3.7AR1
-4¸
(4.0)*
FRN4.0AR1
-4E
̈
5.5
FRN5.5AR1
-4¸
̈
7.5
FRN7.5AR1
-4¸
̈
11
FRN11AR1
-4¸
̈
15
FRN15AR1
-4¸
̈
18.5
FRN18.5AR1
-4¸
̈
22
FRN22AR1
-4¸
̈
30
FRN30AR1
-4¸
̈
37
FRN37AR1
-4¸
* 4.0 kW for the EU. The inverter type is FRN4.0AR1
̈
Note: A box (
) replaces an alphabetic letter depending on the enclosure.
A box (¸) replaces an alphabetic letter depending on the shipping destination.
*1 The frame size and model of the MCCB or RCD/ELCB (with overcurrent protection) will vary, depending on the
power transformer capacity. Refer to the User's Manual for details.
*2 The recommended wire size for main circuits is for the 70°C 600 V PVC wires used at a surrounding temperature
of 40°C.
10. The inverter has been tested with IEC61800-5-1 2007 short-circuit test under the following conditions.
Short-circuit current in the supply: 10,000 A
Maximum 480 V
Recommended wire size (mm
MCCB or
Main terminal
RCD/ELCB
1
Main power input
*
Rated
[L1/R, L2/S,
Inverter's
current
L3/T]
grounding
2
*
[ G]
5
10
2.5
10
15
20
30
40
4
6
50
10
75
16
100
25
̈
-4E.
vii
2
)
Aux.
control
Inverter
Control
outputs
power
circuit
supply
[U, V, W]
2
*
[R0, T0]
2.5
0.75
2.5
4
6
10
16
25