Chapter 7
SPECIFICATIONS

7.1 Standard Model

Three-phase 400 V class series
Item
̈-
Type (FRN_ _ _AR1
4¸)
Nominal applied motor (kW)
Rated capacity (kVA)
Output
ratings
Rated current (A)
Rated current (A)
Input
power
Required capacity (kVA)
EMC filter (IEC/EN 61800-3: 2004)
DC reactor (DCR)
Fundamental
Power factor
wave power factor
(at the rated load)
Total power factor
Efficiency (at the rated load)
Cooling method
IP21
Weight / Mass (kg)
IP55
Site location
IP00/
IP21
Surrounding
temperature
IP55
Relative humidity
Environmental
Requirements
Atmosphere
Altitude
Atmospheric
pressure
Vibration
̈
*1 A box (
) replaces an alphabetic letter depending on the enclosure. A box (¸) replaces an alphabetic letter depending
on the shipping destination.
*2 Fuji 4-pole standard motor
*3 When the inverter is connected to the power supply of 400 V, 50 Hz, Rsce = 120.
*4 4.0 kW for the EU.
*5 Do not install the inverter in an environment where it may be exposed to lint, cotton waste or moist dust or dirt which will
clog the heat sink of the inverter. If the inverter is to be used in such an environment, install it in a dustproof panel of
your system.
*6 If you use the inverter in an altitude above 1000 m, you should apply an output current derating factor as listed in the
table below.
Altitude
1000 m or lower
Output current
1.00
derating factor
3.7
0.75
1.5
2.2
5.5
*1
(4.0)
*4
3.7
0.75
1.5
2.2
5.5
*2
(4.0)
*4
1.9
3.1
4.1
6.8
10
2.5
4.1
5.5
9.0
13.5
1.6
3.0
4.3
7.4
10.3
*3
1.2
2.1
3.0
5.2
7.2
Compliant with EMC Directives, Emission and Immunity: Category C2 (2nd Env.)
Available as standard (IEC/EN 61000-3-2, IEC/EN 61000-3-12)
> 0.98
≥ 0.90
95%
96%
96%
96%
97%
Fan cooling
10
10
10
10
10
10
10
10
10
10
Indoors
-10 to +50°C
-10 to +40°C when inverters of 37 kW or below are mounted
(
side-by-side without any clearance between them.)
-10 to +40°C
-10 to +30°C when inverters of 37 kW or below are mounted
(
side-by-side without any clearance between them.)
5 to 95% (No condensation)
The inverter must not be exposed to dust, direct sunlight, corrosive gases,
flammable gases, oil mist, vapor or water drops.
Pollution degree 2 (IEC60664-1)
The atmosphere can contain a small amount of salt.
2
(0.01 mg/cm
or less per year)
The inverter must not be subjected to sudden changes in temperature that will
cause condensation to form.
1,000 m max.
*6
86 to 106 kPa
3 mm
2 to less than 9 Hz
2
10 m/s
9 to less than 200 Hz
1000 to 1500 m
1500 to 2000 m
0.97
0.95
7-1
Specifications
7.5
11
15
18.5
22
7.5
11
15
18.5
22
14
18
24
29
34
18.5
24.5
32
39
45
13.9
20.7
27.9
34.5
41.1
9.7
15
20
24
29
96%
97%
97%
97%
97%
10
18
18
18
18
10
18
18
18
18
*5
2000 to 2500 m
2500 to 3000 m
0.91
30
37
30
37
45
57
60
75
55.7
69.4
39
49
97% 97%
23
23
23
23
0.88