System Configuration and Functions
 Reference: Bidirectional Muting
Shown below is an example of bidirectional muting with 4 retro-reflective photoelectric sensors.
It can be used for applications of workpiece approaching from both directions.
Connect outer muting sensors A1 and A2 to the muting input 1 and inner muting sensors B1 and B2 to
the muting input 2.
1. Workpiece approaching from the left
2. Muting from an opposite direction is available as well
Turning muting sensors ON in an order from
A2 to B2 sets F3SJ to a muting status.
This arrangement example uses regressive reflection type E3Z-R series as a muting sensor.
Arrangement must take mutual interference into account.
Muting sensors must be installed so that a distance D3 between muting sensors A1 and A2 should be
smaller than workpiece length L.
As a muting sensor, a transmission or regressive reflection type photoelectric switch, proximity
switch(3-wire type), or limit switch can be used. Two-wire type muting sensor cannot be used.
Distances d2 & D2 between muting sensors: p.47
F3SJ-A
50
User's Manual
A1
Workpiece
V
B1
B2
A2
Turning muting sensors ON in an order from
A1 to B1 sets F3SJ to a muting status.
F3SJ
A1, A2, B1, B2: Retro-reflective photoelectric sensor
A1 B1
B2 A2
V
F3SJ
d2
d2
D3
Connect to muting Input 1
Connect to muting Input 2
Workpiece
L