Installation Guide
Stop difference
Circuit
2
One DHW tank temperature sensor:
Set the number of degrees above the desired DHW temperature that will
stop the DHW heating (charging).
Two DHW tank temperature sensors:
Set the number of degrees above the desired DHW temperature but
measured by the lower tank temperature sensor that will stop the DHW
heating (charging).
–50 ... 50: Set the number of degrees.
94
DEN-SMT/DK
ECL Comfort 210 / 310, application A237 / A337
12194
Setting range
Factory setting
–50 ... 50 K
3 K
One DHW tank temperature sensor (example with positive 'Stop
difference' value):
Temp.
DHW heating
One DHW tank temperature sensor (example with negative 'Stop
difference' value):
Temp.
DHW heating
Two DHW tank temperature sensors, upper and lower
Temp.
DHW heating
VI.LG.R1.02
Stop difference
Desired DHW temp.
Time
Stop difference
Desired DHW temp.
Time
Upper DHW temp. sensor
Stop difference
Desired DHW temp.
Lower DHW temp. sensor
Time
Danfoss District Energy