2.5.5 Electrical connections, Pt 1000 temperature sensors and signals
A237/ A337:
Terminal
Sensor / description
29 and 30 S1
Outdoor temperature
sensor*
28 and 30 S2
Room temperature sensor** ESM-10
27 and 30 S3
Flow temperature sensor*** ESM-11 / ESMB /
26 and 30 S4
DHW charging temperature
sensor (A237.2 / A337.2 only)
Return temperature sensor
25 and 30 S5
24 and 30 S6
DHW tank temperature
sensor, upper****
23 and 30 S7
Flow / heat meter (ECL 210
only)
22 and 30 S8
DHW tank temperature
sensor, lower
21 and 30 S9
ECL 310 only:
Not used
20 and 30 S10 ECL 310 only:
Voltage signal (0 - 10 V) for
external control of desired
flow temperature
*
If the outdoor temperature sensor is not connected or the
cable is short-circuited, the controller assumes that the
outdoor temperature is 0 (zero) °C.
**
Only for room temperature sensor connection. The room
temperature signal can alternatively be available from a
Remote Control Unit (ECA 30 / 31). See 'Electrical connections,
ECA 30 / 31'.
*** The flow temperature sensor must always be connected
in order to have the desired functionality. If the sensor is
not connected or the cable is short-circuited, the motorized
control valve closes (safety function).
**** This sensor is used if only one tank temperature sensor is
required.
Factory established jumper:
30 to common terminal.
36
DEN-SMT/DK
ECL Comfort 210 / 310, application A237 / A337
Type
(recomm.)
ESMT
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESMB /
ESMU
ESMB /
ESMU
S8
S6
S5
S4
VI.LG.R1.02
ECL 210 / 310
ECL 310
S3
S2
S1
Danfoss District Energy
B
A
B
A
B
A
B
A