Installation Guide
Application A337.2
ECL 310 / 24 V a.c.
Terminal
Description
19
Phase for alarm output
18
Alarm
17
Do not use
16
Phase for DHW charging pump, circuit 2
15
K4
DHW charging pump ON / OFF, circuit 2
14
Phase for circulation pumps / changeover valve
13
K3
DHW circulation pump ON / OFF, circuit 2
12
K2
DHW pump ON / OFF, circuit 2 / changeover valve
11
K1
Heating circulation pump ON / OFF, circuit 1
10
Supply voltage 24 V a.c. - neutral (N)
9
Supply voltage 24 V a.c. - live (L)
8
M1
Phase for motorized control valve output, circuit 1
7
M1
Motorized control valve - opening
6
M1
Motorized control valve - closing
5
M2
Phase for motorized changeover valve output, circuit 2 (DHW)
4
M2
Motorized changeover valve, DHW circuit direction
3
M2
Motorized changeover valve, heating circuit direction
2
Do not use
1
Do not use
* Relay contacts: 4 A for ohmic load, 2 A for inductive load
Factory established jumpers:
5 to 8, 9 to 14, L to 5 and L to 9, N to 10
34
DEN-SMT/DK
ECL Comfort 210 / 310, application A237 / A337
VI.LG.R1.02
Max. load
4 (2) A / 24 V a.c.*
4 (2) A / 24 V a.c.*
4 (2) A / 24 V a.c.*
4 (2) A / 24 V a.c.*
4 (2) A / 24 V a.c.*
1 A / 24 V a.c.
1 A / 24 V a.c.
1 A / 24 V a.c.
1 A / 24 V a.c.
Danfoss District Energy