Danfoss ECL Comfort 210 Installation Manual page 80

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
MENU > Settings > Optimization
Pre-stop (optimized stop time)
Circuit
1
Disable the optimized stop time.
OFF:
The optimized stop time is disabled.
ON:
The optimized stop time is enabled.
MENU > Settings > Optimization
Based on (optimization based on room / outdoor temp.)
Circuit
1
The optimized start and stop time can be based on either room or outdoor
temperature.
OUT:
Optimization based on outdoor temperature. Use this
setting if the room temperature is not measured.
ROOM:
Optimization based on room temperature, if measured.
MENU > Settings > Optimization
Total stop
Circuit
1
Decide whether you want a total stop during the saving temperature period.
OFF:
No total stop. The desired flow temperature is reduced
according to:
• desired room temperature in saving mode
• auto saving
ON:
The desired flow temperature is lowered to the set value
in 'Frost pr. ' The circulation pump is stopped but frost
protection is still active, see 'P frost T'.
80
DEN-SMT/DK
ECL Comfort 210 / 310, application A237 / A337
11026
Setting range
Factory setting
OFF / ON
ON
11020
Factory setting
Setting range
OUT / ROOM
OUT
11021
Factory setting
Setting range
OFF / ON
OFF
Example: Optimization of Comfort from 07:00 - 22:00
07:00
Optimization start
Desired flow temp. °C
Desired flow temp. °C
The min. flow temperature limitation ('Temp. min.') is overruled when
'Total stop' is ON.
VI.LG.R1.02
22:00
Schedule
Pre-stop OFF
Pre-stop ON
Optimization stop
Total stop = ON
'Frost pr.'
Time
Total stop = OFF
'Frost pr.'
Time
Danfoss District Energy