Installation Guide
MENU > Settings > Optimization
Summer, cut-out
Circuit
1
The heating can be switched OFF when the outdoor temperature is
higher than the set value. The valve closes and after the post-run
time, the heating circulation pump stops. 'Temp. min. ' will be
overruled.
The heating system switches ON again when the outdoor
temperature and the accumulated (filtered) outdoor temperature
become lower than the set limit.
This function can save energy.
Set the value for outdoor temperature at which you want the
heating system to switch OFF.
See also "Heat cut-out" (MENU > Settings > Heat cut-out).
Parallel operation
Circuit
1
Choose whether the heating circuit is to operate parallel to the DHW circuit.
OFF:
DHW heating has 100% priority. The heating circuit
circulation pump is OFF during DHW heating
1 ... 99 K: Dependent parallel operation. The heating circuit
circulation pump is ON if the difference between DHW
heating temperature (charging temperature) and
desired flow temperature is less than the set value.
Danfoss District Energy
ECL Comfort 210 / 310, application A237 / A337
11179
Setting range
Factory setting
OFF / 1 ... 50 °C
20 °C
11043
Setting range
Factory setting
OFF / 1 ... 99 K
Temp.
Actual outdoor temp.
18 °C
Heating ON
The heating cut-out is only active when the controller mode is in
scheduled operation. When the cut-out value is set to OFF, there is
no heating cut-out.
Temp.
OFF
100% DHW
Parallel operation
priority
VI.LG.R1.02
Accumulated outdoor temp.
Heating OFF
Heating ON
Acceptable difference
DHW heating temp.
Desired heating flow temp.
Time
Time
DEN-SMT/DK
81