Pt 1000 temperature sensor (IEC 751B, 1000 Ω / 0 °C)
Danfoss District Energy
ECL Comfort 210 / 310, application A237 / A337
Relationship between temperature and ohmic value:
°C
1600
-50
803
1500
-40
843
-30
882
-20
922
1400
-10
961
0
1000
1300
10
1039
20
1078
30
1117
1200
40
1155
50
1194
1100
60
1232
70
1271
1000
80
1309
90
1347
100
1385
900
110
1423
120
1461
800
130
1498
140
1535
150
1573
VI.LG.R1.02