Installation Guide
Input type, ECL Key A2xx
Circuit
1
Choice of pulse type signal applied to input S7. Possible in ECL Comfort 210
as well as ECL Comfort 310 controllers.
OFF:
No input.
IM1:
Pulse.
Input type, ECL Key A3xx
Circuit
1
Choice of M-bus signal from energy meter number 1 ... 5. Only possible
in ECL Comfort 310.
OFF:
No M-bus signal acquired.
EM1 ... EM5: Energy meter number.
Units, ECL Key A2xx
Circuit
1
Choice of units for measured values. Choose a value in the range 1 ... 9999
in 'Pulse' .
Units to the left: pulse value.
Units to the right: actual and limitation values.
The value from the flow meter is expressed as ml or l.
The value from the heat meter is expressed as Wh, kWh, MWh or
GWh.
The values for the actual flow and the flow limitation are expressed
as l/h or m³/h.
The values for the actual power and the power limitation are
expressed as kW, MW or GW.
76
DEN-SMT/DK
ECL Comfort 210 / 310, application A237 / A337
11109
Setting range
Factory setting
OFF / IM1
11109
Setting range
Factory setting
OFF / EM1 ... EM5
11115
Setting range
Factory setting
See the list
ml, l/h
Flow or power limitation is based on pulse signals.
OFF
Flow or power limitation is based on M-bus signal (ECL Comfort 310
OFF
controllers only).
List for setting range of 'Units':
ml, l/h
l, l/h
ml, m³/h
l, m³/h
Wh, kW
kWh, kW
kWh, MW
MWh, MW
MWh, GW
GWh, GW
Example 1:
'Units' (11115):
l, m³/h
10
'Pulse' (11114):
Each pulse represents 10 litres and the flow is expressed as cubic
meters (m³) per hour.
Example 2:
'Units' (11115):
kWh, kW (= kilo Watt hour, kilo Watt)
1
'Pulse' (11114):
Each pulse represents 1 kilo Watt hour and the power is
expressed in kilo Watt.
VI.LG.R1.02
Danfoss District Energy