Danfoss ECL Comfort 210 Installation Manual page 70

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
MENU > Settings > Room limit
Infl. - min. (room temp. limitation, min.)
Circuit
1
Determines how much the desired flow temperature will be influenced
(increased) if the actual room temperature is lower than the desired room
temperature (P control).
0.0:
The room temperature has no influence.
9.9:
The room temperature has a big influence.
MENU > Settings > Room limit
Adapt. time (adaption time)
Circuit
1
Controls how fast the actual room temperature adapts to the desired room
temperature (I control).
OFF:
The control function is not influenced by the 'Adapt.
time'.
1:
The desired room temperature is adapted quickly.
50:
The desired room temperature is adapted slowly.
70
DEN-SMT/DK
ECL Comfort 210 / 310, application A237 / A337
11183
Setting range
Factory setting
0.0 .... 9.9
0.0
11015
Setting range
Factory setting
OFF / 1 ... 50 s
OFF
The adaptation function can correct the desired flow temperature
with max. 8 K x heat curve value.
VI.LG.R1.02
Danfoss District Energy