MENU > Settings > Return limit
Adapt. time (adaptation time)
Circuit
1
Controls how fast the return temperature adapts to the desired return
temperature limit (I control).
OFF:
The control function is not influenced by the 'Adapt.
time' .
1:
The desired temperature is adapted quickly.
50:
The desired temperature is adapted slowly.
MENU > Settings > Return limit
Priority (priority for return temp. limitation)
Circuit
1
Choose whether the return temperature limitation should overrule the set
min. flow temperature 'Temp. min.' .
OFF:
The min. flow temperature limit is not overruled.
ON:
The min. flow temperature limit is overruled.
Danfoss District Energy
ECL Comfort 210 / 310, application A237 / A337
11037
Setting range
Factory setting
OFF / 1 ... 50 s
25 s
11085
Setting range
Factory setting
OFF / ON
OFF
The adaptation function can correct the desired flow temperature
with max. 8 K.