Vacon NX User Manual page 63

Liquid-cooled drives
Hide thumbs Also See for NX:
Table of Contents

Advertisement

INSTALLATION
Table 23. Max temperatures of coolant at switching frequency of 3.6 kHz
Supply voltage 525-690 VAC, switching frequency 3,6 kHz
Chassis
Type
CH61
NXP0261_6
CH62
NXP0502_6
CH63
NXP0750_6
CH64
NXP1500_6
CH72
NXP0502_6
CH74
NXP1500_6
Table 24. Max temperatures of coolant at switching frequency of 1.5 kHz
Supply voltage 525-690 VAC, switching frequency 1,5 kHz
Chassis
Type
CH61
NXP0261_6
CH62
NXP0502_6
CH63
NXP0750_6
CH64
NXP1500_6
CH72
NXP0502_6
CH74
NXP1500_6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Max coolant temperature [°C]
Supply voltage 525 V
1)
45 (43)
1)
41 (39)
1)
42 (40)
1)
41 (39)
1)
38 (36)
1)
41 (39)
Max coolant temperature [°C]
Supply voltage 525 V
1)
54 (52)
1)
52 (50)
1)
53 (51)
1)
52 (50)
1)
51 (49)
1)
52 (50)
vacon • 61
Max coolant temperature [°C]
Supply voltage 690 V
1)
39 (37)
1)
33 (31)
1)
36 (34)
1)
34 (32)
1)
32 (30)
1)
34 (32)
Max coolant temperature [°C]
Supply voltage 690 V
1)
51 (49)
1)
47 (45)
1)
50 (48)
1)
47 (45)
1)
46 (44)
1)
48 (46)
5