TECHNICAL DATA
Table 1. Power ratings of NX Liquid-Cooled frequency converter (6-pulse),
Mains voltage 400-500 VAC, 50/60 Hz, 3~, 6-pulse drives
3710_5
3710
4140_5
4140
Table 2. Power ratings of NX Liquid-Cooled frequency converter (12-pulse),
Mains voltage 400-500 VAC, 50/60 Hz, 3~, 12-pulse drives
Converter
Thermal
type
Rated cont. I
I
th
[A]
0460_5
460
0520_5
520
0590_5
590
0650_5
650
0730_5
730
1370_5
1370
1640_5
1640
2060_5
2060
2470_5
2470
2950_5
2950
3710_5
3710
4140_5
4140
I
= Thermal maximum continuous RMS current. Dimensioning can be done according to this current if the
th
process does not require any overloadability or the process does not include any load variation or margin for
overloadability.
I
= Low overloadability current. Allows +10% load variation. 10% exceeding can be continuous.
L
I
= High overloadability current. Allows +50% load variation. 50% exceeding can be continuous.
H
All values with cosϕ = 0,83 and efficiency = 97%.
*) c = power loss into coolant; a = power loss into air; T = total power loss; power losses of input chokes not
included. All power losses obtained using max. supply voltage, I
Closed Loop control mode. All power losses are worst case losses.
If some other mains voltage is used, apply the formula
Liquid-Cooled drive output power.
The enclosure class for all NX Liquid-Cooled frequency converters is IP00.
If the motor is continuously (besides start and stop ramps) run at frequencies below 5 Hz, pay attention to the
drive dimensioning for low frequencies, i.e. maximum I
recommended to check the rating with your distributor or Vacon.
Drive overrating may also be necessary if the process requires high starting torque.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
supply voltage 400-500 VAC
3372
2473
3763
2760
supply voltage 400-500 VAC
Drive output
Current
Rated
L
contin. I
motor at I
H
[A]
[A]
(400 V) [kW]
418
307
473
347
536
393
591
433
664
487
1245
913
1491
1093
1873
1373
2245
1647
2681
1967
3372
2473
3763
2760
1950
2450
2150
2700
Motor output power
Optimum
Optimum
motor at I
th
th
(500 V) [kW]
250
315
250
355
315
400
355
400
400
450
700
900
850
1050
1050
1350
1300
1600
1550
1950
1950
2450
2150
2700
and switching frequency of 3.6 kHz and
th
P =
x Un x In x cosϕ x eff%
3
= 0.66*I
or choose drive according to I
H
th
vacon • 19
58.2/3.0/61.2
2*CH74
65.0/3.6/68.6
2*CH74
Power loss
*)
Chassis
c/a/T
[kW]
6.5/0.5/7.0
CH72
7.5/0.6/8.1
CH72
9.0/0.7/9.7
CH72
10.0/0.7/10.7
CH72
12.0/0.8/12.8
CH72
19.0/1.2/20.2
CH74
24.0/1.4/25.4
CH74
32.5/1.8/34.3
CH74
38.8/2.2/41.0
2*CH74
46.3/2.6/48.9
2*CH74
58.2/3.0/61.2
2*CH74
65.0/3.6/68.6
2*CH74
to calculate the NX
. It is
H
4