Vacon NX User Manual page 31

Liquid-cooled drives
Hide thumbs Also See for NX:
Table of Contents

Advertisement

TECHNICAL DATA
Analogue input voltage
Analogue input current
Digital inputs (6)
Auxiliary voltage
Control
connections
(apply to boards
OPT-A1, OPT-A2
Output reference voltage
and OPT-A3)
Analogue output
Digital outputs
Relay outputs
Overvoltage trip limit
Undervoltage trip limit
Earth fault protection
Mains supervision
Motor phase supervision
Unit overtemperature
Protections
protection
Overcurrent protection
Motor overload protection Yes *
Motor stall protection
Motor underload
protection
Short-circuit protection of
+24 V and +10 V reference
voltages
* Note: System software version NXP00002V186 (or newer) must be used for the motor thermal memory and
memory retention functionality to conform to UL 508C requirements. If an older system software version
is used, motor overtemperature protection is required at installation to comply with UL requirements.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Table 9. Technical data
0...+10 V, R
= 200 kΩ, (–10 V...+10 V joystick control)
i
Resolution 0.1%, accuracy ±1%
0(4)...20 mA, Ri = 250 W differential
Positive or negative logic; 18...24 VDC
+24 V, ±10%, max volt. ripple < 100 mVrms;
max. 250 mA
Dimensioning: max. 1000 mA/control box
1A external fuse required (no internal short-circuit
protection on the control board)
+10 V, +3%, max. load 10 mA
0(4)...20 mA; R
Accuracy ±2%
Open collector output, 50 mA/48 V
2 programmable change-over relay outputs
Switching capacity: 24 VDC/8 A, 250 VAC/8 A,
125 VDC/0.4 A
Min. switching load: 5 V/10 mA
NX_5: 911 VDC
NX_6: (CH61, CH62, CH63 & CH64): 1258 VDC
NX_6: (CH72 & CH74): 1200 VDC
NX_8: (CH61, CH62, CH63 & CH64): 1300 VDC
NX_5: 333 VDC; NX_6: 461 VDC; NX_8: 461 VDC
In case of earth fault in motor or motor cable, only
the frequency converter is protected.
Trips if any of the input phases is missing
(frequency converters only).
Trips if any of the output phases is missing.
Alarm limit: 65 ºC (heatsink); 75 ºC (circuit boards).
Trip limit: 70 ºC (heatsink); 85 ºC (circuit boards).
Yes
Motor overload protection provided at 110% of full
motor load current.
Yes
Yes
Yes
max. 500 Ω; Resolution 10 bit;
L
vacon • 29
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents