Settings - Siemens SIPROTEC 7RW80 Manual

Voltage and frequency protection
Hide thumbs Also See for SIPROTEC 7RW80:
Table of Contents

Advertisement

2.6.3

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
Addr.
Parameter
0
FLEXIBLE FUNC.
0
OPERRAT. MODE
0
MEAS. QUANTITY
0
MEAS. METHOD
0
PICKUP WITH
0
VOLTAGE
0
VOLTAGE SYSTEM
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
T TRIP DELAY
0A
T PICKUP DELAY
0A
T DROPOUT DELAY
0A
BLK.by Vol.Loss
SIPROTEC, 7RW80, Manual
C53000-G1140-C233-1, Release date 10.2010
Setting Options
OFF
ON
Alarm Only
3-phase
1-phase
no reference
Please select
Voltage
Frequency
df/dt rising
df/dt falling
Binray Input
dV/dt rising
dV/dt falling
Fundamental
True RMS
Positive seq.
Negative seq.
Zero sequence
Exceeding
Dropping below
Please select
Va-n
Vb-n
Vc-n
Va-b
Vb-c
Vc-a
Vn
Vx
Phase-Phase
Phase-Ground
2.0 .. 260.0 V
2.0 .. 200.0 V
40.00 .. 60.00 Hz
50.00 .. 70.00 Hz
0.10 .. 20.00 Hz/s
2.0 .. 260.0 V
4 .. 100 V/s
0.00 .. 3600.00 sec
0.00 .. 60.00 sec
0.00 .. 60.00 sec
NO
YES
Default Setting
OFF
Flexible Function
3-phase
Mode of Operation
Please select
Selection of Measured Quantity
Fundamental
Selection of Measurement
Method
Exceeding
Pickup with
Please select
Voltage
Phase-Phase
Voltage System
110.0 V
Pickup Threshold
110.0 V
Pickup Threshold
51.00 Hz
Pickup Threshold
61.00 Hz
Pickup Threshold
5.00 Hz/s
Pickup Threshold
110.0 V
Pickup Threshold
60 V/s
Pickup Threshold
1.00 sec
Trip Time Delay
0.00 sec
Pickup Time Delay
0.00 sec
Dropout Time Delay
YES
Block in case of Meas.-Voltage
Loss
Functions
2.6 Flexible Protection Functions
Comments
87