Siemens SIPROTEC 7RW80 Manual page 198

Voltage and frequency protection
Hide thumbs Also See for SIPROTEC 7RW80:
Table of Contents

Advertisement

Technical Data
4.9 User-defined Functions (CFC)
Device-specific Limits
Maximum number of synchronous
changes of chart inputs per task level
Maximum number of chart outputs per
task level
Additional Limits
Task Level
MW_BEARB
PLC1_BEARB
PLC_BEARB
SFS_BEARB
1)
When the limit is exceeded, an error message is output by the device. Consequently, the device starts mon-
itoring. The red ERROR-LED lights up.
2)
The following condition applies for the maximum number of timers: (2 · number of TIMER + number of
TIMER_SHORT) < 30. TIMER and TIMER_SHORT hence share the available timer resources within the
frame of this inequation. The limit does not apply to the LONG_TIMER.
3)
The time values for the blocks TIMER and TIMER_SHORT must not be selected shorter than the time res-
olution of the device of 10 ms, as the blocks will not then start with the starting pulse.
Maximum Number of TICKS in the Task Levels
MW_BEARB (measured value processing)
PLC1_BEARB (slow PLC processing)
PLC_BEARB (fast PLC processing)
SFS_BEARB (interlocking)
1)
When the sum of TICKS of all blocks exceeds the limits mentioned before, an error message is output in the
CFC.
198
Designation
Additional limits
2) 3)
TIMER
Task level
Limit
165
When the limit is exceeded, an error message is output by
the device. Consequently, the device starts monitoring. The
red ERROR-LED lights up.
150
1)
for the following CFC blocks:
Maximum Number of Modules in the Task Levels
TIMER_SHORT
15
Comment
2) 3)
30
Limit in TICKS
10000
2000
400
10000
SIPROTEC, 7RW80, Manual
C53000-G1140-C233-1, Release date 10.2010
1)