Transfer Of Measured Values; Information List - Siemens SIPROTEC 7RW80 Manual

Voltage and frequency protection
Hide thumbs Also See for SIPROTEC 7RW80:
Table of Contents

Advertisement

Functions
2.12 Auxiliary Functions

2.12.3.2 Transfer of Measured Values

Measured values can be transferred to a central control and storage device via port B.
The measuring range in which these values are transmitted depend on the protocol and, if necessary, additional
settings.
Protocol
IEC 60870–5–103
IEC 61850
PROFIBUS,
Modbus, DNP 3.0

2.12.3.3 Information List

No.
Information
621
Va =
622
Vb =
623
Vc =
624
Va-b=
625
Vb-c=
626
Vc-a=
627
VN =
629
V1 =
630
V2 =
632
Vsync =
644
Freq=
765
V/f =
766
V/f th=
832
Vo =
30800
VX =
30801
Vph-n =
120
Transmittable measuring range, format
0 to 240 % of the measured value.
The primary operational measured values are transmitted.
The measured values as well as their unit format are set out in detail in manual PIXIT
7RW80.
The measured values are transmitted in „Float" format. The transmitted measuring
range is not limited and corresponds to the operational measurement.
The unit format of the measured values on the device side is at first automatically gen-
erated by means of the selected nominal values of voltage within the system data.
The current unit format can be determined in DIGSI or at the device via Menu Opera-
tional Values.
The user can select via DIGSI which operational measured values (primary, secondary
or percentage) must be transmitted.
The measured values are always transmitted as 16-bit values including sign (range ±
32768). The user can define the scaling of the operational measured value to be trans-
mitted. This will result in the respective transmittable measuring range.
For further details, please refer to the descriptions and protocol profiles.
Type of In-
formation
MV
MV
MV
MV
MV
MV
MV
MV
MV
MV
MV
MV
MV
MV
MV
MV
Comments
Va
Vb
Vc
Va-b
Vb-c
Vc-a
VN
V1 (positive sequence)
V2 (negative sequence)
Vsync (synchronism)
Frequency
(V/Vn) / (f/fn)
Calculated temperature (V/f)
Vo (zero sequence)
Voltage VX
Voltage phase-neutral