Communication Interfaces - Siemens SIPROTEC 7RW80 Manual

Voltage and frequency protection
Hide thumbs Also See for SIPROTEC 7RW80:
Table of Contents

Advertisement

Technical Data
4.1 General Device Data
4.1.4

Communication Interfaces

Operator Interface
Terminal
Operation
Transmission speed
Bridgeable distance
Port A
Ethernet electrical for DIGSI
Port B
IEC 60870-5-103
single
RS232
RS485
178
Front side, non-isolated, USB type B socket for connecting a
personal computer
Operation from DIGSI V4.82 via USB 2.0 full speed
With DIGSI
up to 12 Mbit/s max.
5 m
Operation
Terminal
Test voltage
Transmission speed
Bridgeable distance
RS232/RS485/FO according to
the order variant
Connection
Test Voltage
Transmission speed
Maximum distance of transmis-
sion
Connection
Test Voltage
Transmission Speed
Maximum distance of transmis-
sion
With DIGSI
Front case bottom, mounting location "A",
RJ45 socket
100BaseT in acc. with IEEE802.3
LED yellow: 10/100 Mbit/s (on/off)
LED green: connection/no connection
(on/off)
500 V; 50 Hz
10/100 Mbit/s
20 m (66 ft)
Isolated interface for data transfer to a
control terminal
Back case bottom, mounting location "B", 9-
pin DSUB socket
500 V; 50 Hz
min. 1 200 Bd, max. 115 000 Bd;
Factory setting 9 600 Bd
15 m
Back case bottom, mounting location "B", 9-
pin DSUB socket
500 V; 50 Hz
min. 1 200 Bd, max. 115 000 Bd;
Factory setting 38 400 Bd
max. 1 km
SIPROTEC, 7RW80, Manual
C53000-G1140-C233-1, Release date 10.2010

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents