De-Energized Switching - Siemens SIPROTEC 7RW80 Manual

Voltage and frequency protection
Hide thumbs Also See for SIPROTEC 7RW80:
Table of Contents

Advertisement

Functions
2.7 SYNCHROCHECK 25
2.7.3

De-energized Switching

Connecting two components of a power system is also possible if at least one of the components is de-ener-
gized and if the measured voltage is greater than the threshold 6106 V>. With a multi-phase connection on the
, all connected voltages must have a higher value than the threshold V> so that the side V
side V
1
as being energized. With a single-phase connection, of course, only the one voltage has to exceed the thresh-
old value.
Besides the release under synchronous conditions, the following additional release conditions can be selected
for the check:
SYNC V1>V2< =
SYNC V1<V2> =
SYNC V1<V2< =
Each of these conditions can be enabled or disabled individually via parameters or binary inputs; combinations
are thus also possible (e.g. release if SYNC V1>V2< or SYNC V1<V2> are fulfilled).
For that reason synchronization with the use of the additional parameter 6113 25 Synchron (configured to
NO) can also be used for the connection of a ground electrode. In such a case, connection is only permissible
when there is no voltage on the load side.
The threshold below which a power system component is considered as being de-energized is defined by pa-
rameter V<. If the measured voltage exceeds the threshold V>, a power system component is considered as
being energized. With a multi-phase connection on the side V
value than the threshold V> so that the side V
tion, of course, only the one voltage has to exceed the threshold value.
Before granting a release for connecting the energized component V
following conditions are checked:
• Is the reference voltage V
• Is the voltage to be synchronized V
• Is the frequency f
After successful completion of the checks, the release is granted.
For connecting the de-energized component 1 to the energized component 2 or the de-energized component
1 to the de-energized component 2, the conditions to be fulfilled correspond to those stated above.
The associated messages indicating the release via the corresponding condition are as follows: „25 V1>
V2<", „25 V1< V2>" and „25 V1< V2<".
Via the binary inputs „>25 V1>V2<", „>25 V1<V2>" and „>25 V1<V2<", the release conditions can also
be issued externally, provided the synchronization is controlled externally.
The parameter TSUP VOLTAGE (address 6111) can be set to configure a monitoring time which requires the
additional release conditions stated above to be present for de-energized connection before connection is al-
lowed.
92
Release on the condition that component V
is de-energized.
Release on the condition that component V
V
is energized.
2
Release on the condition that component V
ergized.
1
above the setting value Vmin and V> but below the maximum voltage Vmax?
1
below the setting valueV<?
2
within the permissible operating range f
1
, all connected voltages must have a higher
1
is considered as being energized. With a single-phase connec-
and the de-energized component V
1
± 3 Hz?
Nom
C53000-G1140-C233-1, Release date 10.2010
is considered
1
is energized and component V
1
is de-energized and component
1
and component V
are de-en-
1
2
SIPROTEC, 7RW80, Manual
2
, the
2