Measurement - Panasonic KW2G User Manual

Eco-power meter
Hide thumbs Also See for KW2G:
Table of Contents

Advertisement

9.2 Measurement

●Electric power input (Main unit, Expansion unit (power measurement))
Phase and wire system
Measurement circuit
Max. measurement circuit
Rating
Input
Allowable measurement
measurement
voltage
Voltage
VT ratio
Rating
Input
measurement
Current
Allowable measurement
current
Cut-off current
Special
Functions
Cut-off voltage
・Instantaneous electric
power
・Integrated electric
power
・Electricity charge
・Conversion value
Current
Accuracy
(without error
in CT and VT)
Voltage
Temperature
characteristics
Hour meter
Frequency
characteristics
Data update cycle
Single-phase two-wire system
Single-phase three-wire system
Three-phase three-wire system
1-circuit
Main unit
(When measuring 1P2W: 2-circuit)
1-circuit
Expansion unit
(When measuring 1P2W: 2-circuit)
8-circuit (When measuring 1P2W: 16-circuit)
(One main unit +7 expansion units)
Single-phase two-wire system: 100-240V AC (Line voltage)
Single-phase three-wire system: 100-120V AC (Phase voltage)
Three-phase three-wire system: 100-240V AC (Line voltage)
85 to 110% of rated input voltage
Single-phase two-wire system: 85-264V AC (Line voltage)
Single-phase three-wire system: 85-132V AC (Phase voltage)
Three-phase three-wire system: 85-264V AC (Line voltage)
1.00 to 99.99 (Set with setting mode)
*Voltage transformer (VT) is required when you measure a load
with voltage over 240VAC (Allowable measurement voltage).
*Secondary voltage rating of VT is 110V.
<Using the dedicated CT>
・5A/50A/100A/250A/400A/600A (Select with setting mode)
<Using a commercial CT with the secondary side current 5A>
・1 to 4000A (Set with setting mode)
*Use CT with secondary side current of 5A when measure 600A or
more.
120% of rated input voltage
0.1 to 50.0%F.S. (Set with setting mode)
Below 5% of rating voltage
(Rating voltage x 0.05 x VT ratio) (Fixed)
±(2.0% F.S.+1 digit)
(at 20℃, rated input, rated frequency, power factor 1)
*Accuracy coverage: 10 to 100% of CT
±(1.0% F.S.+1 digit)
(at 20℃, rated input, rated frequency, power factor 1)
*Accuracy coverage: 10 to 100% of rated current
±(1.0% F.S.+1 digit)
(at 20℃, rated input, rated frequency, power factor 1)
±(1.0% F.S.+1 digit)
(Range of -10 to 50℃, rated input, power factor 1)
±(0.01%.+1 digit) (at 20℃)
±(1.0% F.S.+1 digit)
(Frequency change±5% based on rated frequency for rated input,
power factor 1)
100ms
115
KW2G / KW2G-H Eco-POWER METER
(common)
(1-power source system)