Transmission format setting mode
Mode defines serial communication (RS485) transmission format (Data length, Parity). Define
the transmission format according to the master's (PLC etc).
・Select from 8bit-o/7bit-n/7bit-E/7bit-o/8bit-n/8bit-E.
'n (none)' means parity is not available.
'E (Even)' means parity is even number.
'o (odd)' means parity is odd number.
*With MODBUS (RTU) protocol, it works only with 8bit.
Press <ITEM/△>,<SET>+<ITEM/△> to change.
8bit-o
Stop bit setting mode
Mode defines serial communication (RS485) stop bit.
・Select from 1 / 2.
Press <ITEM/△> to change.
Response time setting mode
Mode defines serial communication (RS485) response time of main unit.
When command is received, it sends response after setting response time passes.
・It can be set the range of 1 to 99 ms.
*For using Data Logger Unit (DLU) or Data Loggert unit(DLL) as a master, the response time of DLU
is under 1.1ms at 19200bps, set 5ms or more for response time of Eco-POWER METER.
Set it using <ITEM/△>,<SET>+<ITEM/△>.
+
7bit-n
7bit-o
1
( 1 to 99ms)
+
7bit-E
+
8bit-n
↓<SET>
2
↓<SET>
↓<SET>
Monitor
43
KW2G/ KW2G-H Eco-POWER METER
n: not available
E: even number
+
o: odd number
+
8bit-E