Unit for pulse output setting mode
Mode defines unit used for pulse output. It defines the unit of integrated electric power for
1-pulse output.
・Select from 0.001/0.01/0.1/1/10/100kWh /AL-P/AL-C/AL-S/Cnt/OUT/Error.
When one of the '0.001/0.01/0.1/1/10/100' [kWh] is set, one pulse is output at reaching the setting
value. When 'AL-P(Power alarm)' is set, alarm is output at the time when instantaneous electric
power is over the setting value. When 'AL-C(Current alarm)' is set, alarm is output at the time when
current is over the setting value. When 'AL-S(Stand-by alarm)' is set, alarm is output at the time
when current is under the setting value and it passes the setting time. When 'Cnt(Count output)' is
set, it output at the time when count value reaches preset value set by preset value setting mode.
When 'OUT' is set, it controls the output via communication.
When 'Error (Error alarm)' is set, alarm is output When SD memory card writing error, battery
shortage, communication error between main unit and expansion unit.
Press <ITEM/△>,<SET>+<ITEM/△> to change.
+
0.001
+
Pulse output width setting mode
Mode defines pulse output width. It defines the width for 1 pulse.
・It is set the range of 1 to 100ms.
Set it using <ITEM/△>, <SET>+<ITEM/△>.
Power alarm setting mode
Mode defines instantaneous electric power used for alarm output.
・It is set the range of 0.00 to 9999.99kW.
Set it using <ITEM/△>,<SET>+<ITEM/△>.
+
0.01
+
100
+
AL-S
(1~100 )
*It is only when 'AL-P' is selected on unit for pulse output setting mode.
(0.00 to 9999.99)
+
0.1
+
AL-P
+
AL-S
↓<SET>
*It is only when 'electric power value' is selected
↓<SET>
↓<SET>
37
KW2G/ KW2G-H Eco-POWER METER
+
1
AL-C
+
OUT
on unit for pulse output setting mode.
Increase
+
Decrease
Increase
Decrease
+
10
Error