Data item
(MEWTOCOL)
0038H
Simple measuring
(DT00056)
0039H<LSB>
(DT00057)
Simple voltage
003AH<MSB>
(DT00058)
003BH
Simple PF
(DT00059)
003DH<LSB>
(DT00061)
【M】
Unit for
Pulse output
003EH<MSB>
(DT00062)
【M】
0040H<LSB>
(DT00064)
Power alarm value
0041H<MSB>
(Instantaneous
(DT00065)
electric power)
0042H
VT ratio
(DT00066)
0044H
Cutoff current
(DT00068)
【M】
0045H
(DT00069)
Ratio for current alarm
0046H
Voltage range
(DT00070)
Calendar Monitor
0047H
(DT00071)
(Hour/Minute)
Calendar timer
0048H
(DT00072)
(Minute/Second)
Calendar timer
0049H
(DT00073)
(Date/Hour)
Calendar timer
004AH
(DT00074)
(Year/Month)
Calendar timer
004BH
(DT00075)
(Day)
004CH
Log cycle setting
(DT00076)
【M】Ratio for stand-by
004DH
(DT00077)
current
【M】Time for stand-by
004EH
(DT00078)
alarm
【M】General-purpose
004FH
(DT00079)
output judgement value
Name
Unit
0.1V
0.01
0.01kW
0.01
0.1%
0.1%
0.1%
1min
Range: Hexadecimal
Kind of data
(Range: Decimal)
Unsigned 16bit
0H(0):OFF 1H(1):ON
Unsigned 32bit
0H to 1869FH (0 to 99999)
Unsigned 16bit
0H to 64H (0 to 100)
1H(1)<0.001>, AH(10)<0.01>,
64H(100)<0.1>,
3E8H(1000)<1>,
2710H(10000)<10>,
186A0H(100000)<100>,
3E7H(999)
< Instantaneous electric power:
378H(888)< Error alarm>
309H(777)
Unsigned 32bit
< Ratio for current alarm:
22BH(555)
< Preset value for output:
14DH(333)
< Ratio and time for Stand-by alarm:
6FH(111)
<General-purpose output type:
Unsigned 32bit
0H to F423FH (0 to 999999)
Unsigned 16bit
64H to 270FH (100 to 9999)
Unsigned 16bit
1H to 1F4H (1 to 500)
Unsigned 16bit
1H to 3E8H (1 to 1000)
Unsigned 16bit
2H(2); 200V <Fixed>
Unsigned 16bit
H:00H to 23H, M:00H to 59H
Unsigned 16bit
M:00H to 59H, S:00H to 59H
Unsigned 16bit
D:01H to 31H, H:00H to 23H
Unsigned 16bit
Y:00H to 99H, M:01H to 12H
Unsigned 16bit
Day:00H to 06H
1H(1)<1>,2H(2)<5>,
Unsigned 16bit
3H(3)<10>,4H(4)<15>,
5H(5)<30>,6H(6)<60>
Unsigned 16bit
1H to 3E8H (1 to 1000)
Unsigned 16bit
0H to 270FH (0 to 9999)
Unsigned 16bit
0H(0):OFF 1H(1):ON
100
KW2G / KW2G-H Eco-POWER METER
Values of 0040H,0041H>
Value of 0045H>
Values of 009EH,009FH>
Value of 004DH,004EH>
Value off 005FH>
MODBUS
Function
code
03H/
06H/10H
03H/
06H/10H
03H/
06H/10H
03H/
06H/10H
03H/
06H/10H
03H/
06H/10H
03H/
06H/10H
03H/
06H/10H
03H
03H
03H/
06H/10H
03H/
06H/10H
03H/
06H/10H
03H/
06H/10H
03H/
06H/10H
03H/
06H/10H
03H/
06H/10H
03H/
06H/10H