<File type 3 (Instantaneous detailed value)>
A
B
(1)
1 No. Date time
1
2012/10/1 0:00
2
(2)
2
2012/10/1 0:15
3
3
2012/10/1 0:30
4
4
2012/10/1 0:45
5
5
2012/10/1 1:00
6
6
2012/10/1 1:15
7
7
2012/10/1 1:30
8
8
2012/10/1 1:45
9
9
2012/10/1 2:00
10
10
2012/10/1 2:15
11
11
2012/10/1 2:30
12
(1) Item
(2) Logging trigger
(3) Record number
(4) Logging data
(4)
C
D
E
kWh
kWh
kW
kW
(row 1) Measured data (Fixed)
Timing to log data: 1,10,15,30,60 min. (selectable with setting mode)
1 min: 00 in every minute
10-min: 0,10,20,30,40,50 in every hour
15-min: 0,15,30,45 in every hour
30-min: 0,30 in every hour
60-min: 00 in every hour
Record number for 1 file:
・Depend on capacity of SD memory card
(In case of inserting SD memory card)
・720 records (in case of not inserting SD memory card)
File creating timing: Same as logging timing
・Record in 1 file regardless f the type
・'-' is recorded for immeasurable items
Logging data of the same timing: 22 data (fixed)
From column C to AC
Integrated electric power(1), Integrated electric power(2),
Instantaneous electric power:
active(1), active(2), reactive(1), reactive(2), apparent(1), apparent(2)
R-current, N/S-current, R/T-current,
R(RS)-voltage, RT-voltage, T(TS)-voltage,
Power factor(1), Power factor(2), Frequency, Count value
CH0 digital conversion value, CH1 digital conversion value,
CH0 pulse count value, CH1 pulse count value
*'Integrated electric power' is logged with the unit of 0.01kWh.
It doesn't log it with the unit of 0.001kWh.
F
G
H
I
kvar
kvar
kVA
58
KW2G-H Eco-POWER METER
J
kVA
(3)