4Th Page Programming Fields - Honeywell VISTA-32FB Programming Manual

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for VISTA-32FB:
Table of Contents

Advertisement

2*09
OPEN/CLOSE REPORTS BY EXCEPTION [0]
1=enable; 0=disable
If enabled, only openings and closings occurring outside the
scheduled opening/closing windows will trigger dialer reports.
Opening reports will also be suppressed during the closing
window, in order to prevent false reports when the user arms
the system and then reenters the premises to retrieve a
forgotten item.
2*10
ALLOW DISARMING ONLY DURING
ARMING/DISARMING WINDOWS
0=disable; 1=enable
See system-wide field 2*11 if enabling field 2*10. This
feature adds high security to the installation.
2*11
ALLOW DISARM OUTSIDE WINDOW
IF ALARM OCCURS
Used only if field 2*10 is set to "1." If this field is enabled ("1")
the system can be disarmed outside the disarm window if an
alarm has occurred. If "0," disarming can only be done during
the disarm window. If field 2*10 is set to "0" for a partition,
this field has no effect for that partition.
2*18
ENABLE GOTO FOR THIS PARTITION
1=Allow log-on from other partitions; 0=disable
NOTE: Must be disabled for partition 1 in Commercial Fire
installations.
2*19
USE PARTITION DESCRIPTORS
0=disable; 1=enable
2*20
ENABLE J2 TRIGGERS FOR PARTITION
0=disable; 1=enable for displayed partition
2*21
ENABLE SUPERVISION PULSES FOR COMM
Not Used. Must Be Set To "00000".
Used only for supervised connection to Communicators (e.g.
7845i-ent).
Enter 0 to disable or 1 to enable the listed outputs.
F= Fire; B= Burglary/Audible Panic; P= Silent Panic/Duress;
S= Supervisory; T= Trouble.
2*22
DISPLAY FIRE ALARMS OF
OTHER PARTITIONS
0=disable; 1=enable.
Must be set to "0" (disable) for partition 1.
2*23
DISPLAY BURG, PANIC and CO
ALARMS OF OTHER PARTITIONS
0=disable; 1=enable.
Must be set to "0" (disable) for partition 1.
2*24
DISPLAY TROUBLES OF OTHER
PARTITIONS
0=disable; 1=enable
Must be set to "0" (disable) for partition 1.

4th Page Programming Fields

3*00
DISPLAY TRBL INSTEAD OF CHECK
0=CHECK; 1=TRBL
3*01
EVENTS DISPLAY LOCK
0=scroll all alarms; 1=lock display of first fire alarm
NOTE: Must be set to "1" for Commercial Fire Installations.
[0]
[0]
[0]
[0]
[1]
-
00000]
F
B
P
S
[0]
[0]
[0]
(press *94)
[0]
[1]
3*12
ZN TYPE 18 DELAY USE
0=disable; 1=enable
NOTE: Must be set to "0" for Commercial Fire Installations.
3*13
FIRE SUPERVISORY RESPONSE TO OPEN/SHORT
(Applies to Zone Type 18)
0=Trouble on open/Supervisory on short
1=Supervisory on open/Supervisory on short
NOTE: Must be set to "0" for Commercial Fire Installations.
3*14
WATERFLOW SILENCE OPTION
0=silence on code = off; 1=silence when waterflow restores
NOTE: Must be set to "0" for Commercial Fire Installations.
3*16
DELAY FOR ZONE TYPE 17 & 18
Enter 00-15 times 2 seconds
Delay cannot exceed 90 seconds in UL installations.
NOTE: Must be "00" for Commercial Fire installations.
3*17
ALTERNATE FUNCTION (TAMPER)
FOR ZONE 6
3*18
EXTENDED DELAY FOR TYPES 17 & 18
0=disable; 1=enable
NOTE: Must be "0" for Commercial Fire installations.
3*19
AUX INPUT ALTERNATE FUNC ENABLE
0=pins 5 and 9 function as per filed 3*20;
1=pins 5 and 9 function as RXD and DTR
NOTE: Must be set to "0" for Commercial Fire Installations.
3*20
TRIGGER OUTPUT SELECTION
0=Communicator full connection & remote console sounder;
1=Communicator limited connection and keyswitch LEDs
2=Communicator fire only connection and 5140LED
NOTE: Must be set to "0" for Commercial Fire Installations.
T
3*21
MAX NUMBER OF DIALER ATTEMPTS
1-8 (3, 4 or 5 for NFPA72 compliant systems when a
secondary phone number is programmed (field *34))
3*30
DIALER SELECTION
0=disable; 1=enable
NOTE: If 3*30 is disabled (0, 0), the panel does not report at
all via Communicator.
3*31
BACKUP DIALER TOUCHTONE/ROTARY
1=TouchTone; 0=Rotary
3*50
ZONE TYPE RESTORE ENABLES
FOR ZONE TYPES 16-18
1=enable; [0=disable]
Restores must be set to "1" for Commercial Fire installations.
3*55
RESET ON SECOND OFF FOR BELL 1
0=disable; 1=enable
NOTE: Must be set to "0" for Commercial Fire Installations.
3*56
RESET ON SECOND OFF FOR BELL 2
0=disable; 1=enable
NOTE: Must be set to "0" for Commercial Fire Installations.
– 12 –
[00]
0=disable; 1=enable
[1,0]
Main Backup
[1]
[0]
[0]
|
[0]
[0]
[0]
[0]
[8]
[1]
[0]
[0]