1*45
EXIT DELAY SOUNDING
1=enable; 0=disable Produces quick beeping during exit
delay if enabled.
NOTES:
Must be set to "0" in partition 1 for fire systems.
See page 31, "SOUND OPTION", prompt for disabling the
entry/exit beeps on individual
1*47
CHIME ON BELL 1
1=enable; 0=disable
1*52
SEND CANCEL IF CODE + OFF
1=no restriction; 0=within Bell Timeout period only.
1*76
CONTROL RELAY FOR PART.
Relay will be pulsed for 2 seconds whenever code + [0] is
pressed. Enter 00-96; 00=none.
Must be "00" for Commercial Burglary and Commercial Fire
installations.

3rd Page Fields

2*05
AUTO-ARM DELAY
Enter the time between the end of the arming window and
the start of auto-arming warning period, in values of 1-14
times 4 minutes 00=instant; [15=no auto arm at all]. When
this delay expires, the Auto-Arm Warning Period begins.
2*06
AUTO-ARM WARNING PERIOD
This is the time during which the user is warned to exit the
premises prior to the auto-arming of the system (beeps every
15 seconds; "ALERT" displayed). Enter 01-15 minutes.
00=instant at end of arming delay.
2*07
AUTO-DISARM DELAY
This is the time between the end of the disarming window
and the start of auto-disarming. Enter 01-14 times 4 minutes;
00=instant at end of window; 15=no auto-disarm
2*08
ENABLE FORCE ARM FOR AUTO-ARM
0=disable; 1=enable
2*09
OPEN/CLOSE REPORTS BY EXCEPTION [0]
1=enable; 0=disable. If enabled only openings and closings
occurring outside the scheduled opening/closing windows
trigger dialer reports. Opening reports will also be
suppressed during the closing window, in order to prevent
false reports when the user arms the system and then re-
enters the premises to retrieve a forgotten item.
2*10
ALLOW DISARMING ONLY DURING
ARMING/DISARMING WINDOWS
See system-wide field 2*11 if enabling field 2*10. This
feature adds high security to the installation.
0=disable; 1=enable
2*18
[0]
ENABLE GOTO FOR THIS PARTITION
1=Allow log-on from other partitions; 0=disable
NOTE: Must be disabled (0) for partition 1 in Commercial
Fire installations.
2*20
ENABLE J2 TRIGGERS BY PARTITION
0=disable for displayed partition; 1=enable for displayed
partition
[0]
2*22
DISPLAY FIRE ALARMS OF
OTHER PARTITIONS
[0]
0=disable; 1=enable
Must be set to "0" (disable) for partition 1.
2*23
DISPLAY BURG, PANIC AND CO ALARMS [0]
|
[00]
OF OTHER PARTITIONS
0=disable; 1=enable
Must be set to "0" (disable) for partition 1.
2*24
DISPLAY TROUBLES OF OTHER
PARTITIONS
0=disable; 1=enable
|
Must be set to "0" (disable) for partition 1.
[15]

4th Page Fields

3*57
BELL 2 & AUX RELAY CONFIRM
ARMING DING
|
[15]
0=disable; 1=enable.
NOTE: If using a keyfob, when the button is pressed, either
for arming or disarming, the bell will ding indicating that the
button is working.
Must be set to "1" for Commercial Burglary installations.
3*59
ENABLE BELL 2 & AUX RELAY
|
[15]
CHIME ANNUNCIATION
0=disable; 1=enable
NOTE: Must be "0, 0" if Bell 2 or Aux. Relay is used for fire
application.
[0]
3*60
BELL 2 & AUX RELAY TIMEOUT
Enter 00-15 times 2 minutes; 00=no timeout [00, 00]
Minimum 16 minutes for Commercial Burglary installations.
SUMMARY OF PROGRAMMING COMMANDS
To enter program mode, enter installer code + [8] + [0] + [0]
To set standard defaults, press *97
To change to next page of program fields, press *94
To return to previous set of fields, press *99
[0]
To erase account and phone number field entries, press [*] +
field number + [*]
To assign zone descriptors, press #93 + follow menu prompts
To add custom words, press #93 + follow menu prompts
To enter Installer's Message, press #93 + follow menu prompts
To exit program mode, enter *99 OR *98: *99 allows re-access
to programming mode by installer code. *98 prevents re-access
to programming mode by installer code.
– 15 –
[0]
[1]
[0]
[0]
[0,0]
Bell 2
Aux
[0, 0]
Bell 2
Aux
|
|
Bell 2
Aux