3Rd Page Programming Fields - Honeywell VISTA-32FB Programming Manual

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for VISTA-32FB:
Table of Contents

Advertisement

1*44
WIRELESS KEYPAD TAMPER DETECTION
Used. Must be set to "0".
1=enable; 0=disable.
1*45
EXIT DELAY SOUNDING
1=enable; 0=disable. Produces quick beeping during exit
delay if enabled.
NOTES:
Must be set to "0" in partition 1 for fire systems.
See page 31, "SOUND OPTION", prompt for disabling the
entry/exit beeps on individual keypads.
1*47
CHIME ON BELL 1
1=enable; 0=disable
1*48
WIRELESS KEYPAD ASSIGNMENT
be set to "0".
0=disable; enter partition in which RF keypad used, 1-2.
1*49
SUPPRESS TX SUPERVISION SOUND
1=disable; 0=enable.
Must be "0" for Commercial Burglary and Fire installs.
1*52
SEND CANCEL IF CODE + OFF
1=no restriction; 0=within bell timeout period only.
1*53
DOWNLOAD CALLBACK
1=callback not required; 0=callback required.
Must be "0" for Commercial Burglary and Commercial Fire
installations.
1*55
EUROPEAN DATE FORMAT
0=disable (mm/dd/yy); 1=enable (dd/mm/yy).
1*56
AC 50/60 Hz CLOCK SPEED
1=50 Hz; 0=60 Hz.
1*57
5800 RF BUTTON GLOBAL ARM
1=enable; 0=disable
Must be "0" for Commercial Burglary and Commercial Fire
installations.
1*58
5800 RF BUTTON FORCE ARM
1=enable. If a zone is faulted after pressing button, console
will beep once. User should press button again within 4 sec.
to force bypass those zones. 0=disable.
Must be "0" for Commercial Burglary and Commercial Fire
installations.
1*60
ZONE 5 AUDIO ALARM VERIFICATION
Enter 1 if 2-way audio (AAV) is being used; Enter 0 if it is not.
Must be "0" for Commercial Burglary and Commercial Fire
installations.
1*70
EVENT LOG TYPES
[1 0 0 0 1 0]
1=enable; 0=disable
1*71
12/24 HOUR TIME STAMP FORMAT
0=12 hour; 1=24 hour
– Not
[0]
[0]
[0]
- Not Used. Must
[0]
[1]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
Alarm Chk
Byp
O/C
Syst
[0]
1*72
EVENT LOG PRINTER ON-LINE -
Set To "0".
0=disable; 1=enable
1*73
PRINTER BAUD RATE -
"0"..
1=300; 0=1200
1*74
RELAY TIMEOUT XXX MINUTES
Enter relay timeout, 0-127 in multiples of 2 minutes, desired
for #80 Menu Mode time-driven event relay command
numbers "04/09" and #93 Menu Mode Output Programming
output command "56."
1*75
RELAY TIMEOUT YYY SECONDS [000]
Enter relay timeout, 0-127 seconds, desired for #80 Menu
Mode time driven event relay command numbers "05/10" and
#93 Menu Mode Output Programming command "57."
1*76
CONTROL RELAY
Relay will be pulsed for 2 seconds whenever code + [0] is
pressed. Enter relay number 01-96; 00=none.
Must be "00" for Commercial Burglary and Commercial Fire
installations.
1*77
LOG FIRST MAINTENANCE SIGNAL
0=No Log; 1=Log first maintenance signal from each smoke
detector.

3rd Page Programming Fields

2*00
NUMBER OF PARTITIONS
Enter 1-2
2*01
DAYLIGHT SAVING TIME
START/END MONTH
00-12; if no daylight saving time, enter 00,00
2*02
DAYLIGHT SAVING TIME
START/END WEEKEND
Enter 1-7. 1=first; 2=second; 3=third; 4=fourth; 5=last; 6=next
to last; 7=3rd from last [1,5]
2*05
AUTO-ARM DELAY
Enter the time between the end of the arming window and the
start of auto-arming warning period, in values of 1-14 times 4
minutes 00=instant; [15=no auto arm at all]. When this delay
expires, the Auto-Arm Warning Period begins.
2*06
AUTO-ARM WARNING PERIOD
This is the time during which the user is warned to exit the
premises prior to the auto-arming of the system (beeps every
15 seconds; "ALERT" displayed). Enter 01-15 minutes.
00=instant at end of arming delay.
Test
2*07
AUTO-DISARM DELAY
This is the time between the end of the disarming window
and the start of auto-disarming. Enter 01-14 times 4 minutes;
00=instant at end of window; 15=no auto-disarm.
2*08
ENABLE FORCE ARM FOR AUTO-ARM
0=disable; 1=enable
– 11 –
Not Used. Must Be
[0]
Not Used. Must Be Set To
[0]
| |
[000]
| |
|
[00]
[0]
(press *94)
[1]
|
|
[03, 11]
Start End
|
[2, 1]
Start | End
|
[15]
|
[15]
|
[15]
[0]