Partition-Specific Fields

(Duplicate this page for each partition in the installation.)
To program these fields,
1. Press *91 to select a partition.
2. Enter a partition-specific field number (ex. *09).
3. Make the required entry.
4. Repeat steps 1-3 for each partition in the system.

1st Page Fields

*09
ENTRY DELAY #1
00, 02-15 times 15 seconds
Maximum "03" for Commercial Burglary installations.
*10
EXIT DELAY #1
00, 03-15 times 15 seconds
Maximum "04" for Commercial Burglary installations.
*11
ENTRY DELAY #2
00, 02-15 times 15 seconds (must be longer than Entry Delay
#1). Maximum "03" for Commercial Burglary installations.
*12
EXIT DELAY #2
00, 03-15 times 15 seconds (must be longer than Exit Delay
#1). Maximum "04" for Commercial Burglary installations.
*13
BELL 1 TIMEOUT
01-15 times 2 minutes. Must be set to a minimum 16 minutes
for Commercial Burglary installations. Must be minimum 6
minutes for Commercial Fire installations.
*16
BELL 1 CONFIRMATION OF ARMING DING [0]
1=enable; 0=disable.
NOTE: If using a keyfob, when the button is pressed, either for
arming or disarming, the bell will ding indicating that the button
is working.
Must be "1" for Commercial Burglary installations.
*22
KEYPAD PANIC ENABLES
1=enable; 0=disable
NOTE: Use for burglary panic types only. Do not use in
partition 1 in Fire systems.
*23
MULTIPLE ALARMS
1=enable; 0=disable.
Must be 1 for Commercial Burglary installations.
*29
QUICK ARM
1=enable; 0=disable
*32
PRIM. SUBS. ACCT #
Enter 00-09; B-F (11-15) [15 15 15 15]
*38
PREVENT ZONE XXX BYPASS
001-032; 000 if all zones can be bypassed
PARTITION #____ PROGRAM FIELDS
|
[02]
|
[03]
|
[06]
|
[08]
|
[03]
[001]
995 996 999
[1]
[1]
|
|
|
| |
[000]
*39
ENABLE OPEN/CLOSE REPORT
FOR INSTALLER CODE
1=enable; 0=disable
*84
SWINGER SUPPRESSION
01-15 alarms;
Must be "00" (disabled) for Commercial Burglary installations.
*85
ENABLE DIALER REPORTS FOR PANICS & DURESS
1=enable; [0=disable]
*87
ENTRY WARNING
1=continuous; 0=3 beeps
*88
BURG. ALARM COMM. DELAY
1=30 seconds; 0=no delay.
Must be "0" for Commercial Burglary installations.
*90
SEC. SUBS. ACCT #
Enter 00-09; B-F (11-15)

2nd Page Fields

1*18
AFFECTS LOBBY
Enter 1 if this partition affects the common lobby; enter 0 if it
does not.
Must be set to "0" for Commercial Burglary and Commercial
Fire installations.
1*19
ARMS LOBBY
Enter 1 if arming this partition attempts to arm lobby; enter 0
if it does not
Must be "0" for Commercial Burglary and Commercial Fire
installations.
1*26
PANIC BUTTON OR SPEEDKEY
[00, 00, 00, 00]
Enter speedkey macro # (01-32) to use keys A-C for macro.
Otherwise enter 00 to use as panic. For D key, enter macro
# 01-32 or 00 to select macro when key is pressed.
|
1*43
PERM. KEYPAD BACKLIGHT
1=enable; 0=disable
When disabled, display lights when any key is pressed, and
turns off after period of keypad inactivity.
– 14 –
[00]
995 996 999 Duress
|
|
|
[15 15 15 15]
|
|
|
|
A
B
C
D
[1]
|
[1]
[0]
|
[0]
[0]
[0]