Relay Voice Descriptors - Honeywell VISTA-32FB Programming Manual

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for VISTA-32FB:
Table of Contents

Advertisement

Relay Voice Descriptors

Each voice descriptor can consist of up to 3 words selected from the Relay Voice Descriptors and Custom Word Substitutes
Vocabulary list (later in this section).
The index numbers from this vocabulary list are to be used for relay voice descriptors only. For normal
system voice annunciation (e.g., alarms, troubles, status), use the highlighted words in the alpha vocabulary
list in the Alpha Programming part of this guide.
To enter relay voice descriptors, do the following:
1.
From Data Field Programming mode, press #93 to display the "ZONE PROG?" prompt.
2.
Press [0] (NO) to each menu option until the "RLY VOICE DESCR?" prompt is displayed. Follow the instructions below.
While in this mode, press [✱] to advance to next screen. Press [#] to back up to previous screen.
PROMPT
RLY VOICE DESCR?
1=YES
0=NO
0
ENTER RELAY NO.
00=QUIT
01
01 ENTER DESC d1
01 ENTER DESC d2
01 ENTER DESC d3
EXPLANATION
Press [1] to program voice descriptors for relays.
Enter the 2-digit relay number (01-32) for the relay desired, or enter 00 to quit Relay Voice Descriptor
Programming Mode.
Press [✱]
From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3-digit index
number for the first word of the relay descriptor phrase.
Press [✱] to accept entry.
From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3-digit index
number for the second word of the relay descriptor phrase. If second word is not desired, press [000].
Press [✱] to accept entry.
From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3-digit index
number for the third word of the relay descriptor phrase. If third word is not desired, press [000].
Press [✱] to accept entry. The "ENTER RELAY NO." prompt appears. Enter the next relay number to be
programmed. When you have programmed all output devices, enter 00 to quit.
Enter ✱99 to exit Program Mode.
– 38 –

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents