STOP (STP):

The "STOP" programming determines when and under what conditions the device is de-activated. The
following options are available:
1). RESTORE ZONE LIST (ZL). If a "ZONE LIST" is used as the "Stop" event, the device de-activates
when all the zones in that list restore from a previous fault, trouble, or alarm condition. This occurs
regardless of what is programmed to "START" the device; therefore, a "RESTORE ZONE LIST" is
normally only used when a "ZONE LIST" is used to start the device.
2). ZONE TYPE/SYSTEM OPERATION (ZT). Instead of using a "RESTORE ZONE LIST," you can select
a specific zone (response) type or system operation action to de-activate the device.
If you choose a specific "ZONE TYPE," any zone of that response type that restores from a previous
alarm, trouble, or fault condition will cause the device to de-activate.
If you choose a "SYSTEM OPERATION," that operation causes the device to de-activate. The
different choices for "ZONE TYPE" and "SYSTEM OPERATION" are listed in "Programming Relays"
later in this section, and in the Programming Form.
3)
PARTITION NO. (P). The device's "Stop" Zone Type/System Operation may be limited to an
occurrence on one partition (1-2), or on any partition (0).
The "ZONE TYPE/SYSTEM OPERATION" option functions independently of the
"RESTORE/ZONE LIST" combination.

Output Devices Programming

From Data Field Programming Mode, press #93 to display the "ZONE PROG?" prompt. Press [0] (NO) to each menu option
until the "OUTPUT PGM?" prompt appears. Press [1] (YES).
While in this mode, press [✱] to advance to next screen. Press [#] to back up to the previous screen.
PROMPT
ENTER RELAY #
(00=QUIT)
01
02
A EV ZL ZT P
STT 0
0 00 00 0
02
A ZL ZT P
STOP
0 00 00 0
02 RELAY ACTION
NO RESPONSE
0
02 START EVENT
NOT USED
0
02 START: ZN LIST
00
02 START: ZONE #
000
02 START: ZN TYPE
NO RESPONSE
00
EXPLANATION
Enter the relay (output device) identification number 01-96. This is a reference number only, used for
identification purposes. The actual module address and relay number on the module are programmed in the
last two prompts.
Press [✱] to continue.
Press [✱] to continue.
The keypad displays a summary STOP screen.
Press [✱] to continue.
The Relay Action is the way in which the relay will respond when activated by the "start" event. Enter the
desired action for this relay as follows:
0=not used; 1=close for 2 secs.; 2=stay closed; 3=pulse on/off; 4= toggle on and off alternately
NOTE: For options 1 and 4, do not program a "Stop" parameter.
An output may be activated by an Event/Zone List combination, and/or by a Zone Type/System Operation.
For an Event/Zone List combination, enter the event code as follows:
0=not used; 1=alarm; 2=fault; 3=trouble
NOTE: An Event is required for Zone List, Zone Number and Zone Types 17 and 18.
If you are not using a Zone List, Zone Number, or Zone Types 17 or 18 to activate the relay, enter 0.
Press [✱] to continue.
A zone list is a set of zones that can be used to initiate the start or stop relay action. If a zone list is being
used to start this relay action, enter the zone list number, 1-15. If a zone list is not being used, enter 0.
Press [✱] to continue.
A specific zone can be used instead of or in addition to an Event/Zone List or Zone Type/System Operation
combination to start the relay action. Enter the 3-digit zone number.
Press [✱] to continue.
A Zone Type/System Operation can be used instead of or in addition to an Event/Zone List combination or
a specific zone to start the relay action. If a Zone Type/System Operation is being used, enter the 2-digit
code as listed in the table that follows.
Press [✱] to continue.
– 35 –