Honeywell VISTA-32FB Programming Manual page 19

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for VISTA-32FB:
Table of Contents

Advertisement

PROMPT
010 SMART CONTACT
1 = YES 0 = NO
010 V-PLEX RELAY?
1 = YES
0 = NO
010 CONS ECP ADDR
(00-30)
01
010 INPUT S/N:
L
AXXX-XXXX
1
010 INPUT S/N:
L
A022-4064
1
010 INPUT S/N:
L
A022-4064
1
EXPLANATION
If input type 3 or 6 was selected, this prompt will be displayed. Enter 1 for devices that monitor maintenance
signals (ex. 5193SD, 5193SDT) or can be used to limit fault signals in the disarmed state (ex. Quest
2260SN). Otherwise, enter 0.
NOTES:
1. The Smart Contact option must ONLY be selected for devices that support the feature, otherwise
unpredictable results may occur.
2. if using the new 5193SD/SDT V-Plex smoke detectors (or older 5192SD/SDT with the maintenance DIP
sw enabled) the "Smart" option must be selected in zone programming or
results may occur if the smoke goes into a High Sens or Low Sens condition.
If you selected input type 6, this prompt is displayed. Enter 1 if using a 4101SN Relay Module for this
zone. Otherwise enter 0.
Press [✱] to continue.
If you selected input type 09, this prompt is displayed. Enter the ECP address of the keypad that is being
used for entry/exit for this access point (00-30).
Press [✱] to continue.
For Serial Number entry and Loop Number entry, do one of the following:
a. Transmit two open and close (or close and open) sequences. For a button-type transmitter, press and
release the button, wait approximately 4 seconds, then press and release the button a second time.
OR
b. Manually enter the 7-digit serial number printed on a label on the transmitter, using the Alpha keypad.
Then press the [✱] key, the cursor moves to the "L" position. You can edit the loop number, if necessary.
When the loop number is acceptable, press [✱].
OR
c. Press key [C] to copy the last serial number enrolled (used when programming a transmitter with several
input loops).
Press [✱] to accept.
The cursor will then move to the Loop column (L) with the previously entered/transmitted serial number
displayed.
Enter the loop number (refer to 5800 Series Transmitters Loop Designations below).
To Delete an Existing Serial Number, enter "0" in the loop number field. The serial number will change to
"0"s.
If "0" was entered in error, simply re-enter the loop number or press [#], and the serial number will return to
the display.
Press [✱] to accept.
The system will then check for a duplicate serial/loop number combination.
If a duplicate serial/loop number combination is found, the keypad will emit a single long beep, and display
the serial number along with a "?" for the loop number, allowing you to re-enter the correct loop number.
If the serial/loop number combination is not a duplicate in the system, a display appears showing the serial
number and loop number entry.
Press [✱] to continue.
– 19 –
when they
enroll unpredictable

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents