Mitsubishi Electric FR-A700 Series Instruction Manual page 26

Hide thumbs Also See for FR-A700 Series:
Table of Contents

Advertisement

Terminal
Terminal
Symbol
Name
10E
Frequency
setting power
supply
10
Frequency
2
setting
(voltage)
Frequency
4
setting
(current)
Frequency
1
setting
auxiliary
Frequency
5
setting
common
*
In the following case, the input resistance is 10kΩ ± 1kΩ while power is off.
⋅ When current input is selected for Pr.73 or Pr.267 for the 3.7K or less
⋅ When the voltage/current input switch is in the OFF position and current input is selected for Pr.73 or Pr.267 for the 5.5K or more
(2) Output signals
Terminal
Terminal
Symbol
Name
A1,
Relay output 1
B1,
(alarm output)
C1
A2,
B2,
Relay output 2
C2
Description
When connecting the frequency setting potentiometer at an initial
status, connect it to terminal 10.
Change the input specifications of terminal 2 when connecting it
to terminal 10E. (Refer to Pr. 73 Analog input selection in
Instruction Manual (applied).)
Inputting 0 to 5VDC (or 0 to 10V, 4 to 20mA) provides the
maximum output frequency at 5V (10V, 20mA) and makes input
and output proportional. Use Pr.73 to switch between input 0 to
5VDC (initial setting) and 0 to 20mADC when the voltage/current
input switch is in the OFF position (initially set to OFF). The
current input is always the same when the voltage/current input
switch is in the ON position (Pr.73 needs to be set to current input).
Inputting 4 to 20mADC (or 0 to 5V, 0 to 10V) provides the maximum
output frequency at 20mA (5V, 10V) makes input and output
proportional. This input signal is valid only when the AU signal is on
(terminal 2 input is invalid). Use Pr.267 to switch between input 4 to
20mA (initial setting) and 0 to 10VDC when the voltage/current input
switch is in the OFF position (initially set to ON). The current input is
always the same when the voltage/current input switch is in the ON
position (Pr.267 needs to be set to current input).
Use Pr. 858 to switch terminal functions.
(Refer to
Instruction Manual (applied).)
Inputting 0 to ±5 VDC or 0 to ±10VDC adds this signal to terminal
2 or 4 frequency setting signal. Use Pr. 73 to switch between the
input 0 to ±5VDC and 0 to ±10VDC (initial setting).
Use Pr. 868 to switch terminal functions.
Common terminal for frequency setting signal (terminal 2, 1 or 4)
and analog output terminal AM. Do not earth (ground).
Description
1 changeover contact output indicates that the inverter
protective function has activated and the output stopped.
Abnormal: No conduction across B-C (Across A-C Continuity),
Normal: Across B-C Continuity (No conduction across A-C)
1 changeover contact output
Wiring
Rated
Refer to
Specifications
page
10VDC
Instruction
Permissible load
Manual
current 10mA
(applied)
5VDC
Permissible load
76, 81
current 10mA
Voltage input:
76, 81
Input resistance
10kΩ ± 1kΩ
Maximum
permissible
voltage 20VDC
Current input:
Input resistance
245Ω ± 5Ω
Maximum
77, 83
permissible
current 30mA
*
Input resistance
10kΩ ± 1kΩ
Instruction
Maximum
Manual
permissible voltage
(applied)
± 20VDC
-- ------ ------- -----
-- ----
Rated
Refer to
Specifications
page
Instruction
Contact capacity:
Manual
230VAC 0.3A
(applied)
(Power
factor=0.4)
Instruction
30VDC 0.3A
Manual
(applied)
21
2