Mitsubishi Electric FR-A700 Series Instruction Manual page 115

Hide thumbs Also See for FR-A700 Series:
Table of Contents

Advertisement

Parameter List
Parameter
STF terminal
178
function selection
STR terminal
179
function selection
RL terminal function
180
selection
RM terminal
181
function selection
RH terminal
182
function selection
RT terminal function
183
selection
AU terminal
184
function selection
JOG terminal
185
function selection
CS terminal
186
function selection
MRS terminal
187
function selection
STOP terminal
188
function selection
RES terminal
189
function selection
110
Incre
Initial
Name
ments
Value
1
60
1
61
1
0
1
1
1
2
1
3
1
4
1
5
1
6
1
24
1
25
1
62
Range
Description
0 to 20,
0: Low-speed operation command
22 to 28,
1: Middle-speed operation command
42 to 44, 60,
2: High-speed operation command
62, 64 to 71,
3: Second function selection
9999
4: Terminal 4 input selection
5: Jog operation selection
0 to 20,
6: Selection of automatic restart after
22 to 28,
instantaneous power failure, flying start
42 to 44, 61,
7: External thermal relay input
62, 64 to 71,
8: Fifteen speed selection
9999
9: Third function
10: Inverter operation enable signal (FR-HC/
MT-HC, FR-CV connection)
0 to 20,
11: FR-HC/MT-HC connection,
22 to 28,
instantaneous power failure detection
42 to 44, 62,
12: PU operation external interlock
64 to 71,
13: External DC injection brake start
9999
14: PID control valid terminal
15: Brake opening completion signal
16: PU-external operation switchover
0 to 20,
17: Load pattern selection forward/reverse
22 to 28,
rotation boost
42 to 44,
18: V/F switch over
62 to 71,
19: Load torque high-speed frequency
9999
20: S-pattern acceleration/deceleration C
switching terminal
22: Orientation command
23: Pre-excitation
24: Output stop
25: Start self-holding selection
26: Control mode changing
27: Torque limit selection
28: Start time tuning
42: Torque bias selection 1*
43: Torque bias selection 2*
44: P/PI control switchover
60: Forward rotation command (assigned to
0 to 20,
STF terminal (Pr. 178) only)
22 to 28,
61: Reverse rotation command (assigned to
42 to 44, 62,
STR terminal (Pr. 179) only)
64 to 71,
62: Inverter reset
9999
63: PTC thermistor input (assigned to AU
terminal (Pr. 184) only)
64: PID forward/reverse action switchover
65: PU-NET operation switchover
66: External-NET operation switchover
67: Command source switchover
68: Conditional position pulse train sign*
69: Conditional position droop pulse clear*
70: DC feeding operation permission
71: DC feeding cancel
9999:No function
* Available only when used with the FR-A7AP.
All
Param
Param
param
eter
eter
eter
copy
clear
clear
: enabled
× : disabled
×
×
×
×
×
×
×
×
×
×
×
×