Mitsubishi Electric FR-A700 Series Instruction Manual page 141

Hide thumbs Also See for FR-A700 Series:
Table of Contents

Advertisement

Causes and corrective actions
Operation Panel
Indication
Name
Description
Check point
Corrective action
Operation Panel
Indication
Name
Description
Check point
Corrective action
Operation Panel
Indication
Name
Description
Check point
Corrective action
Operation Panel
Indication
Name
Description
Check point
Corrective action
*1
Resetting the inverter initializes the internal thermal integrated data of the electronic thermal relay function.
Operation Panel
Indication
Name
Description
Check point
Corrective action
136
E.OV2
Regenerative overvoltage shut-off during constant speed
If regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the
specified value, the protective circuit is activated to stop the inverter output. The circuit may also be
activated by a surge voltage produced in the power supply system.
Check for sudden load change.
· Keep load stable.
· Use regeneration avoidance function (Pr. 882 to Pr. 886). (Refer to
· Use the brake unit or power regeneration common converter (FR-CV) as required.
E.OV3
Regenerative overvoltage shut-off during deceleration or stop
If regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the
specified value, the protective circuit is activated to stop the inverter output. The circuit may also be
activated by a surge voltage produced in the power supply system.
Check for sudden speed reduction.
· Increase the deceleration time. (Set the deceleration time which matches the inertia of moment of
the load)
· Decrease the braking duty.
· Use regeneration avoidance function (Pr. 882 to Pr. 886). (Refer to
· Use the brake unit or power regeneration common converter (FR-CV) as required.
E.THT
Inverter overload shut-off (electronic thermal relay function)
If a current not less than 150% of the rated output current flows and overcurrent shut-off does not occur
(220% or less), inverse-time characteristics cause the electronic thermal relay to be activated to stop
the inverter output in order to protect the output transistors. (overload immunity 150% 60s)
Check the motor for use under overload.
Reduce the load weight.
E.THM
Motor overload shut-off (electronic thermal relay function)
The electronic thermal relay function in the inverter detects motor overheat due to overload or reduced
cooling capability during constant-speed operation and pre-alarm (TH display) is output when the
temperature reaches 85% of the Pr. 9 Electronic thermal O/L relay setting and the protection circuit is
activated to stop the inverter output when the temperature reaches the specified value. When running
a special motor such as a multi-pole motor or multiple motors, provide a thermal relay on the inverter
output side since such motor(s) cannot be protected by the electronic thermal relay function.
1. Check the motor for use under overload.
2. Check that the setting of Pr. 71 Applied motor for motor selection is correct. (Refer to
Manual (applied).)
3. Check that stall prevention operation setting is correct.
1. Reduce the load weight.
2. For a constant-torque motor, set the constant-torque motor in Pr. 71 Applied motor.
3. Check that stall prevention operation setting is correct. (Refer to
E.FIN
Fin overheat
If the heatsink overheats, the temperature sensor is actuated to stop the inverter output.
The FIN signal can be output when the temperature becomes approximately 85% of the heatsink
overheat protection operation temperature.
For the terminal used for the FIN signal output, assign the function by setting "26" (positive logic) or
"126" (negative logic) in any of Pr. 190 to Pr. 196 (output terminal function selection). (Refer to
Instruction Manual (applied))
1. Check for too high ambient temperature.
2. Check for heatsink clogging.
3. Check that the cooling fan is stopped. (Check that
1. Set the ambient temperature to within the specifications.
2. Clean the heatsink.
3. Replace the cooling fan.
FR-PU04
Stedy Spd OV
FR-PU07
FR-PU04
OV During Dec
FR-PU07
FR-PU04
Inv. Overload
FR-PU07
*1
FR-PU04
Motor Overload
FR-PU07
*1
FR-PU04
H/Sink O/Temp
FR-PU07
is displayed on the operation panel.)
Instruction Manual (applied).)
Instruction Manual (applied).)
Instruction
Instruction Manual (applied).)

Advertisement

Table of Contents
loading

Table of Contents