Parameter List
Parameter
Terminal 2
125
frequency setting
gain frequency
Terminal 4
126
frequency setting
gain frequency
Analog input display
241
unit switchover
Terminal 2
C2
frequency setting
(902)
bias frequency
Terminal 2
C3
frequency setting
(902)
bias
Terminal 2
C4
frequency setting
(903)
gain
Terminal 4
C5
frequency setting
(904)
bias frequency
Terminal 4
C6
frequency setting
(904)
bias
Terminal 4
C7
frequency setting
(905)
gain
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04/FR-PU07).
106
Incre
Initial
Name
ments
Value
0.01Hz
60Hz
0.01Hz
60Hz
1
0
0.01Hz
0Hz
0.1%
0%
0.1%
100%
0.01Hz
0Hz
0.1%
20%
0.1%
100%
Range
Description
Set the frequency of terminal 2 input gain
0 to 400Hz
(maximum).
Set the frequency of terminal 4 input gain
0 to 400Hz
(maximum).
(Valid when Pr. 858 = 0 (initial value))
0
Displayed in %
1
Displayed in V/mA
Set the frequency on the bias side of
0 to 400Hz
terminal 2 input.
Set the converted % of the bias side
0 to 300%
voltage (current) of terminal 2 input.
Set the converted % of the gain side
0 to 300%
voltage of terminal 2 input.
Set the frequency on the bias side of
0 to 400Hz
terminal 4 input.
(Valid when Pr. 858 = 0 (initial value))
Set the converted % of the bias side
0 to 300%
current (voltage) of terminal 4 input.
(Valid when Pr. 858 = 0 (initial value))
Set the converted % of the gain side
0 to 300%
current (voltage) of terminal 4 input.
(Valid when Pr. 858 = 0 (initial value))
Param
Param
eter
eter
copy
clear
: enabled
× : disabled
×
×
Select the unit for
analog input display.
×
×
×
×
×
×
All
param
eter
clear