Mitsubishi Electric FR-A700 Series Instruction Manual page 118

Hide thumbs Also See for FR-A700 Series:
Table of Contents

Advertisement

Parameter
Name
Life alarm status
255
display
Inrush current limit
256
circuit life display
Control circuit
257
capacitor life
display
Main circuit
258
capacitor life
display
Main circuit
259
capacitor life
measuring
Power failure stop
261
selection
Subtracted
262
frequency at
deceleration start
Subtraction starting
263
frequency
Power-failure
264
deceleration time 1
Power-failure
265
deceleration time 2
Power failure
deceleration time
266
switchover
frequency
UV avoidance
294
voltage gain
Incre
Initial
Range
ments
Value
Display whether the control circuit
capacitor, main circuit capacitor, cooling
1
0
(0 to 15)
fan, and each parts of the inrush current
limit circuit has reached the life alarm
output level or not. Reading only
Display the deterioration degree of the
1%
100%
(0 to 100%)
inrush current limit circuit. Reading only
Display the deterioration degree of the
1%
100%
(0 to 100%)
control circuit capacitor. Reading only
Display the deterioration degree of the
1%
100%
(0 to 100%)
main circuit capacitor. Reading only
The value measured by Pr. 259 is displayed.
Setting "1" and turning the power supply off
starts the measurement of the main circuit
capacitor life.
1
0
0, 1
When the Pr.259 value is "3" after powering
on again, the measuring is completed.
Read the deterioration degree in Pr.258.
Coasting to stop
0
When undervoltage or power failure
occurs, the inverter output is shut off.
1
Without UV avoidance When undervoltage
11
With UV avoidance
1
0
2
Without UV avoidance When undervoltage
12
With UV avoidance
Normally operation can be performed with
the initial value unchanged. But adjust the
0.01Hz
3Hz
0 to 20Hz
frequency according to the magnitude of
the load specifications (moment of inertia,
torque).
When output frequency ≥ Pr. 263
0 to 120Hz
0.01Hz
60Hz
When output frequency < Pr. 263
Decelerate from the speed obtained from
9999
output frequency minus Pr. 262.
0.1/
0 to 3600/
Set a deceleration slope down to the
5s
0.01s
360s
frequency set in Pr. 266.
0 to 3600/
Set a deceleration slope below the
0.1/
360s
frequency set in Pr. 266.
9999
0.01s
9999
Same slope as in Pr. 264
Set the frequency at which the
0.01Hz
60Hz
0 to 400Hz
deceleration slope is switched from the Pr.
264 setting to the Pr. 265 setting.
Adjust response level at UV avoidance
operation. A larger setting will improve
responsiveness to the bus voltage change.
0.1%
100%
0 to 200%
Since the regeneration amount is large
when the inertia is large, decrease the
setting value.
Description
or a power failure
occurs, the inverter
can be decelerated
to a stop.
or a power failure
occurs, the inverter
can be decelerated
to a stop.
If power is restored
during a power
failure, the inverter
accelerates again.
Decelerate from the speed obtained
from output frequency minus Pr. 262.
Decelerate from output frequency
Parameter List
All
Param
Param
param
eter
eter
eter
copy
clear
clear
: enabled
× : disabled
×
×
×
×
×
×
×
×
×
×
×
×
3
113