Parameter List
Parameter
96
Refer to Pr. 82 to Pr. 84.
100
V/F1(first frequency)
V/F1(first frequency
101
voltage)
V/F2(second
102
frequency)
V/F2(second
103
frequency voltage)
V/F3(third
104
frequency)
V/F3(third
105
frequency voltage)
V/F4(fourth
106
frequency)
V/F4(fourth
107
frequency voltage)
108
V/F5(fifth frequency)
V/F5(fifth frequency
109
voltage)
Refer to page 98.
71
110, 111
Refer to Pr. 7.
112
Refer to Pr. 0.
113
Refer to Pr. 3.
114, 115
Refer to Pr. 22.
116
Refer to Pr. 41.
PU communication
117
station number
PU communication
118
speed
PU communication
119
stop bit length
PU communication
120
parity check
Number of PU
121
communication
retries
PU communication
122
check time interval
PU communication
123
waiting time setting
104
Incre
Initial
Name
ments
Value
0.01Hz
9999
0.1V
0V
0.01Hz
9999
0.1V
0V
0.01Hz
9999
0.1V
0V
0.01Hz
9999
0.1V
0V
0.01Hz
9999
0.1V
0V
1
0
1
192
1
1
1
2
1
1
0.1s
9999
1
9999
Range
Description
0 to 400Hz,
9999
0 to 1000V
0 to 400Hz,
9999
0 to 1000V
0 to 400Hz,
Set each points (frequency, voltage) of V/F
9999
pattern.
9999: No V/F setting
0 to 1000V
0 to 400Hz,
9999
0 to 1000V
0 to 400Hz,
9999
0 to 1000V
Specify the inverter station number.
Set the inverter station numbers when two
0 to 31
or more inverters are connected to one
personal computer.
Set the communication speed.
The setting value × 100 equals the
48, 96, 192,
communication speed.
384
For example, the communication speed is
19200bps when the setting value is "192".
0
Stop bit length: 1bit data length: 8bit
1
Stop bit length: 2bit data length: 8bit
10
Stop bit length: 1bit data length: 7bit
11
Stop bit length: 2bit data length: 7bit
0
Without parity check
1
With odd parity check
2
With even parity check
Set the permissible number of retries at
occurrence of a data receive error.
0 to 10
If the number of consecutive errors
exceeds the permissible value, the inverter
will come to an alarm stop.
If a communication error occurs, the
9999
inverter will not come to an alarm stop.
0
No PU connector communication
Set the communication check time interval.
If a no-communication state persists for
0.1 to 999.8s
longer than the permissible time, the
inverter will come to an alarm stop.
9999
No communication check
Set the waiting time between data
0 to 150ms
transmission to the inverter and response.
9999
Set with communication data.
All
Param
Param
param
eter
eter
eter
copy
clear
clear
: enabled
× : disabled