Parameter
Name
61
Reference current
Reference value at
62
acceleration
Reference value at
63
deceleration
Starting frequency
64
for elevator mode
Automatic
acceleration/
292
deceleration
Acceleration/
deceleration
293
separate selection
65
Retry selection
Number of retries at
67
alarm occurrence
Retry waiting time
68
Retry count display
69
erase
66
Refer to Pr. 22 and Pr. 23.
67 to 69
Refer to Pr. 65.
70
Refer to Pr. 30.
Incre
Initial
Range
ments
Value
Setting value (rated motor current) is referenced
0 to 500/
* The increments and setting range differ
0.01/
0 to 3600A
9999
*
0.1A
*
9999
Rated inverter current is referenced
Setting value is a limit
value
0 to 220%
Setting value is an
optimum value
0.1%
9999
150% is a limit value
9999
100% is an optimum
value
Setting value is a limit
value
0 to 220%
Setting value is an
optimum value
0.1%
9999
150% is a limit value
9999
100% is an optimum
value
0 to 10Hz
0 to 10Hz are starting frequency
0.01Hz
9999
9999
2Hz is starting frequency
0
Normal mode
1
Shortest acceleration/
deceleration mode
11
3
Optimum acceleration/deceleration mode
1
0
5
Elevator mode 1
6
Elevator mode 2
7
Brake sequence mode 1
8
Brake sequence mode 2
Calculate acceleration/deceleration time of
both acceleration and deceleration for the
0
shortest and optimum acceleration/
deceleration mode.
Calculate only acceleration time for the
1
0
1
shortest and optimum acceleration/
deceleration mode
Calculate only deceleration time for the
2
shortest and optimum acceleration/
deceleration mode
1
0
0 to 5
An alarm for retry can be selected.
0
No retry function
Set the number of retries at alarm
1 to 10
occurrence. An alarm output is not provided
during retry operation.
1
0
Set the number of retries at alarm
occurrence. (The setting value minus 100 is
101 to 110
the number of retries.) An alarm output is
provided during retry operation.
Set the waiting time from when an inverter
0.1s
1s
0 to 10s
alarm occurs until a retry is made.
Clear the number of restarts succeeded by
1
0
0
retry.
Description
according to the inverter capacity. (55K or
less/75k or more)
Shortest acceleration/
deceleration mode
Optimum
acceleration/
deceleration mode
Shortest acceleration/
deceleration mode
Optimum
acceleration/
deceleration mode
Shortest acceleration/
deceleration mode
Optimum
acceleration/
deceleration mode
Shortest acceleration/
deceleration mode
Optimum
acceleration/
deceleration mode
Without brake
With brake
Parameter List
All
Param
Param
param
eter
eter
eter
copy
clear
clear
: enabled
× : disabled
3
97